Safety Incidents OSHA Severe Injury Reports · 2015–2025
2,004,209Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: OUR SISTER'S PLACE, INC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of OUR SISTER'S PLACE, INC. in 580 NORTH US HWY 1, TEQUESTA, FL 33469 (NAICS 624190). OSHA activity number 343762506.

Watch OUR Sister'S Place, INC. — free Get an email when a new federal OSHA severe-injury report for OUR Sister'S Place, INC. is published. One employer, no account, unsubscribe in one click.
Site address
580 NORTH US HWY 1
City
TEQUESTA
State
FL
ZIP
33469
Mailing
580 NORTH US HWY 1, TEQUESTA, FL 33469
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
624190
Employees
3
Ownership type
A

4 citations on file for this inspection.

1910.36 G02

Serious Gravity 5 1 instance 3 exposed
Issued
Penalty
Initial $2273.00 · Current $1137.00 Reduced
29 CFR 1910.36(g)(2): Exit access(es) were not at least 28 inches (71.1 cm) wide at all points:    On or about February 5, 2019, in the receiving/sorting room of the establishment located at 580 N. U.S. Highway in Tequesta, Florida, employees were exposed to trip hazards when working in the receiving/sorting room while the aisle leading to the exit discharge was not maintained at least 28 inches in width.
Recent events (2)
  • — I (S) $1137
  • — Z (S) $2273

1910.303 G01 I B

Serious Gravity 5 1 instance 3 exposed
Issued
Penalty
Initial $2273.00 · Current $1137.00 Reduced
29 CFR 1910.303(g)(1)(i)(B): For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the width of the working space in front of electrical equipment was less than the width of the equipment or 762 mm (30 inches), whichever was greater:    On or about February 5, 2019, in the southwest corner of the receiving/sorting inside the establishment located at 580 N. U.S. Highway in Tequesta, Florida, employees were exposed to struck-by/caught-between hazards from a mobile plastic bin and fluorescent light bulbs being stored in front of, and approximately 15.5 inches away, from an electrical panel, impeding the panel door from opening.
Recent events (2)
  • — I (S) $1137
  • — Z (S) $2273

1910.305 G01 IV A

Serious Gravity 5 1 instance 3 exposed
Issued
Penalty
Initial $2273.00 · Current $1137.00 Reduced
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:    On or about February 5, 2019, in the showroom of the establishment located at 580 N. U.S. Highway in Tequesta, Florida, employees were exposed to shock hazards when electrical extension cords were used as fixed wiring of the structure to energize lighting fixtures.
Recent events (2)
  • — I (S) $1137
  • — Z (S) $2273

1910.303 B02

Serious Gravity 5 1 instance 3 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:   On or about February 5, 2019, in the showroom of the establishment located at 580 N. U.S. Highway in Tequesta, Florida, employees were exposed to shock hazards when using Relocatable Power Taps that were series-connected and/or connected to extension cords to energize lighting fixtures.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 343762506.