OSHA Inspection: IMAGE PLASTICS, INC.

Complaint inspection · Health discipline

On , OSHA opened a complaint health inspection of IMAGE PLASTICS, INC. in 1110 W. CENTER ST., CHETEK, WI 54728 (NAICS 326199). OSHA activity number 343787156.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Image Plastics, INC. — free Get an email when a new federal OSHA severe-injury report for Image Plastics, INC. is published. One employer, no account, unsubscribe in one click.
Site address
1110 W. CENTER ST.
City
CHETEK
State
WI
ZIP
54728
Mailing
PO BOX 84, CHETEK, WI 54728
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
326199
Employees
8
Ownership type
A

19 citations on file for this inspection.

1910.29 B01

Serious Gravity 5 1 instance 2 exposed
Issued
Apr 1, 2019
Abate by
May 6, 2019
Penalty
Initial $2,273 · Current $1,818 Reduced
29 CFR 1910.29(b)(1): A top rail, or equivalent guardrail system member, 42 inches (107 cm), plus or minus 3 inches (8 cm), above the walking-working surface was not installed:    (a) Production Area, New Extrusion Line; The end of the guardrail system on the Crammer platform did not have a top rail installed per standard requirements.
Recent events (2)
  • — I (S) $1818
  • — Z (S) $2273

1910.29 B02

Serious Gravity 5 2 instances 2 exposed
Issued
Apr 1, 2019
Abate by
May 6, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.29(b)(2): Midrails, screens, mesh, intermediate vertical members, or equivalent intermediate structure members were not installed between the top edge of the guardrail system and the walking/working surface when there was no wall or parapet wall at least 21 inches (53 cm) high:  (a) Production Area, Old Extrusion Line; The guardrail system installed on the Crammer platform did not have midrails.   (b) Production Area, New Extrusion Line; The end guardrail installed on the Crammer platform does not have a midrail installed per standard requirements.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.95 G01

Serious Gravity 5 2 instances 7 exposed
Issued
Apr 1, 2019
Abate by
May 6, 2019
Penalty
Initial $3,410 · Current $2,728 Reduced
29 CFR 1910.95(g)(1): The employer did not establish and maintain an audiometric testing program as provided by 29 CFR 1910.95(g) by making audiometric testing available to all employees whose exposures equal or exceed an 8-hour time-weighted average (TWA) of 85 decibels:    (a) Production Area; A Grinder Operator was exposed to continuous noise at levels greater than 85 dBA during the 455 minute sampling period on February 14, 2019 (zero exposure was assumed for the unsampled time period of 25 minutes). The operator was exposed at an eight-hour time weighted average (TWA) of 97.20 dBA (dose of 271.4%). The employer did not provide audiometric testing for the employee who exceeded the 8-hour TWA of 85 decibels.     (b) Production Area; A forklift operator was exposed to continuous noise at levels greater than 85 dBA during the 438 minute sampling period on February 14, 2019 (zero exposure was assumed for the unsampled time period of 42 minutes). The employee was exposed at an eight-hour time weighted average (TWA) of 89.09 dBA (dose of 88.13 %). The employer did not provide audiometric testing for the employee who exceeded the 8-hour TWA of 85 decibels.
Recent events (2)
  • — I (S) $2728
  • — Z (S) $3410

1910.95 K02

Serious Gravity 5 2 instances 7 exposed
Issued
Apr 1, 2019
Abate by
May 6, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.95(k)(2): The training program was not repeated annually for each employee included in the hearing conservation program:  (a) Production Area; A Grinder Operator was exposed to continuous noise at levels greater than 85 dBA during the 455 minute sampling period on February 14, 2019 (zero exposure was assumed for the unsampled time period of 25 minutes). The operator was exposed at an eight-hour time weighted average (TWA) of 97.20 dBA (dose of 271.4%). The employer did not provide training annually (training provided last on January 7, 2015) for the employee who exceeded the 8-hour TWA of 85 decibels.   (b) Production Area; A forklift operator was exposed to continuous noise at levels greater than 85 dBA during the 438 minute sampling period on February 14, 2019 (zero exposure was assumed for the unsampled time period of 42 minutes). The employee was exposed at an eight-hour time weighted average (TWA) of 89.09 dBA (dose of 88.13 %). The employer did not provide training annually (training provided last on January 7, 2015) for the employee who exceeded the 8-hour TWA of 85 decibels.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.212 A03 II

Serious Gravity 5 1 instance 1 exposed
Issued
Apr 1, 2019
Abate by
May 6, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.212(a)(3)(ii): Point(s) of operation of machinery were not guarded to prevent employee(s) from having any part of their body in the danger zone(s) during operating cycle(s):  (a) Production Area; The guillotine shear utilized to cut polyethylene rolls was not adequately guarded at the point of operation.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.219 C02 I

Serious Gravity 5 1 instance 3 exposed
Issued
Apr 1, 2019
Abate by
May 6, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.219(c)(2)(i): All exposed part(s) of horizontal shafting seven (7) feet or less from floor or working platform were not protected by stationary casing(s) enclosing shafting completely or by trough(s) enclosing sides and top or sides and bottom of shafting:  (a) Production Area, Old Extrusion Line; The extruder does not have adequate guarding at the base of the machine to protect employees from the rotating shaft.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.303 B02

Deleted Serious Gravity 5 1 instance 7 exposed
Issued
Apr 1, 2019
Abate by
May 6, 2019
Penalty
Initial $3,410 · Current $0 Reduced
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:  (a) Production Area, Old Extrusion Line; Electrical installation of pendant box was not in accordance with manufacturers listing and labeling as the pendant box had pre-punched knockouts and was used with a flexible cord.
Recent events (2)
  • — I (S) $0
  • — Z (S) $3410

1910.303 B07

Serious Gravity 5 1 instance 7 exposed
Issued
Apr 1, 2019
Abate by
May 6, 2019
Penalty
Initial $0 · Current $2,728
29 CFR 1910.303(b)(7): Electrical equipment was not installed in a neat and workmanlike manner:    (a) Production Area, Old and New Extrusion Line;  Electrical equipment was not adequately installed in order to enclose insulated conductors and components to prevent exposure to bare live ends and to protect electrical wires from damage.
Recent events (2)
  • — I (S) $2728
  • — Z (S) $0

1910.303 B07 III

Serious Gravity 5 1 instance 7 exposed
Issued
Apr 1, 2019
Abate by
May 6, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(7)(iii): Internal parts of electrical equipment, including busbars, wiring terminals, insulators, and other surfaces, may not be damaged or contaminated by foreign materials such as paint, plaster, cleaners, abrasives, or corrosive residues:    (a) Production Area, Old and New Extrusion Line; Internal parts of electrical equipment  were covered in foreign material and subject to corrosion in several areas where 110 and 480 volt systems were utilized.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.303 E01 II

Serious Gravity 5 1 instance 1 exposed
Issued
Apr 1, 2019
Abate by
May 6, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.303(e)(1)(ii): Electrical equipment was not marked giving voltage, current, wattage or other ratings as necessary:  (a) Production Area; 480 volt electrical panels were not marked giving voltage, current, and other ratings as required.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.303 G02 I

Serious Gravity 5 1 instance 7 exposed
Issued
Apr 1, 2019
Abate by
May 6, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating  at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i):  (a) Production Area, Old Extrusion Line; Cooling Fan had a 110 volt live wire that was not adequately guarded by use of  an approved enclosure.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.304 G05

Serious Gravity 5 1 instance 7 exposed
Issued
Apr 1, 2019
Abate by
May 6, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective:  (a) Production Area, Old Extrusion Line; 110 volt cooling fans were not adequately grounded.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 B01 I

Serious Gravity 5 1 instance 7 exposed
Issued
Apr 1, 2019
Abate by
May 6, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(1)(i): Openings through which conductors entered cutout boxes, cabinets, or fittings were not effectively closed:  (a) Production Area, Old Extrusion Line; 480 volt box, located above and adjacent to water system, had opening(s) through which conductors entered and were not effectively closed.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 B01 II

Serious Gravity 5 3 instances 7 exposed
Issued
Apr 1, 2019
Abate by
May 6, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed:  (a) Production Area, Old Extrusion Line; 480 volt boxes, located above and adjacent to water system, had opening(s) that were not effectively closed.  (b) Production Area, New Extrusion Line; 480 volt boxes, located above and adjacent to water system, had opening(s) that were not effectively closed.  (c) Production Area, New Line Extruder Drive Panel; 480 volt panel(s) were not effectively closed on the front bottom of the panel.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 B02 I

Deleted Serious Gravity 5 1 instance 7 exposed
Issued
Apr 1, 2019
Abate by
May 6, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(2)(i): Covers of outlet boxes having holes through which flexible cord pendants passed were not provided with bushings designed for the purpose nor did the holes have smooth, well-rounded surfaces on which the cords could bear:  (a) Production Area, Old Extrusion Line; Flexible cords utilized with pendant were not provided with bushings designed for the purpose.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 G02 III

Serious Gravity 5 1 instance 7 exposed
Issued
Apr 1, 2019
Abate by
May 6, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws:  (a) Production Area, Old Extrusion Line; Flexible cords were not provided with adequate strain relief.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.147 C05 II

Other-than-serious 1 instance 1 exposed
Issued
Apr 1, 2019
Abate by
May 6, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.147(c)(5)(ii): Lockout devices and tagout devices were not used for lockout and tagout purposes only:  (a) Outside water tank; Lockout/tagout devices were being used to lockout equipment that was no longer being used for production operations.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.178 Q01

Other-than-serious 2 instances 5 exposed
Issued
Apr 1, 2019
Abate by
May 6, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.178(q)(1): Any power-operated industrial truck not in safe operating condition was not taken out of service, and/or repairs were not made by authorized personnel:  (a) Warehouse Area; The Toyota Forklift Model 426FGCU18 (s/n 67836) did not have an operable horn and seat belt and was not taken out of service until repairs were performed.   (b) Production Area; The Raymond electric standup lift Model DSS 300 TF (s/n S300-02296-98) did not have an operable horn and was not taken out of service until repairs were performed.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.178 Q07

Other-than-serious 1 instance 5 exposed
Issued
Apr 1, 2019
Abate by
May 6, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.178(q)(7): Powered industrial truck(s) which were used on a round-the-clock basis were not examined for defects after each shift:  (a) Production Area; Powered industrial trucks were not inspected per shift.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View Image Plastics, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 343787156.