BRONX, NY —
OSHA Inspection: URBAN INTERIORS MANAGEMENT INC
Complaint inspection · Health discipline
At a glance
On , OSHA opened a complaint health inspection of URBAN INTERIORS MANAGEMENT INC in 375 E 163RD ST, BRONX, NY 10451 (NAICS 238350). OSHA activity number 343787388.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- URBAN INTERIORS MANAGEMENT INC
- Site address
- 375 E 163RD ST
- City
- BRONX
- State
- NY
- ZIP
- 10451
- Mailing
- 375 E 163RD ST, BRONX, NY 10451
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 238350
- Employees
- 5
- Ownership type
- A
Citations
6 citations on file for this inspection.
1910.107 B05 IV
- Issued
- Apr 22, 2019
- Penalty
- Initial $2,273 · Current $0 Reduced
General-duty citation text
29 CFR 1910.107(b)(5)(iv): Space within the spray booth on the downstream and upstream sides of filters were not protected with approved automatic sprinklers. Location: Inside the spray booth a) The spray booth did not have automatic sprinklers located on the upstream sides; on or about 1/31/19
Recent events (3)
- — J (S) $0
- — C (S) $2273
- — Z (S) $2273
1910.107 C07
- Issued
- Apr 22, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.107(c)(7): Electric lamps outside of but within 20 feet of spraying area(s), and not separated therefrom by partition(s), were not protected from mechanical injury by suitable guards or by location. Location: Spray booth area a) Fluorescent lights located within 20ft of spraying area were not covered with a guard; on or about 2/14/19
Recent events (3)
- — J (S) $0
- — C (S) $0
- — Z (S) $0
1910.157 E03
- Issued
- Apr 22, 2019
- Penalty
- Initial $1,705 · Current $0 Reduced
General-duty citation text
29 CFR 1910.157(e)(3): The annual maintenace record was not retained for one year after the last entry or the life of the shell, whichever is less: Location: Spray Booth Area a) The fire extinguisher located next to the spray booth was inspected in 2017; on or about 2/14/19. b) The fire extinguisher located outside of the spray booth room did not have an inspection tag; on or about 2/14/19.
Recent events (3)
- — J (S) $0
- — C (S) $1705
- — Z (S) $1705
1910.157 C04
- Issued
- Apr 22, 2019
- Abate by
- Apr 30, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(c)(4): The employer did not assure that portable fire extinguishers were maintained in a fully charged and operable condition and kept in their designated places at all times except during use: Location: Spray Booth Area a) Two Type A fire extinguishers were not in operable or kept in their designated places; on or about 2/15/19.
Recent events (3)
- — J (S) $0
- — C (S) $0
- — Z (S) $0
1910.1200 E01
- Issued
- Apr 22, 2019
- Abate by
- May 16, 2019
- Penalty
- Initial $1,705 · Current $0 Reduced
General-duty citation text
29 CFR 1910.1200(e)(1): The employer did not develop, implement, and/or maintain at the workplace a written hazard communication program which describes how the criteria specified in 29 CFR 1910.1200(f), (g), and (h) will be met: Location: Office a) Employee use and handle hazardous chemicals such as but not limited to gloss paints and paint thinner (Toluene ,Aliphatic Hydrocarbon solvent and Butyl Acetate ) in the manufacturing of custom built furniture; on or about 1/31/19.
Recent events (3)
- — J (S) $0
- — C (S) $1705
- — Z (S) $1705
1910.1200 H01
- Issued
- Apr 22, 2019
- Abate by
- May 16, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.1200(h)(1): Employees were not provided effective information and training on hazardous chemicals in their work area at the time of their initial assignment and whenever a new hazard that the employees had not been previously trained about was introduced into their work area: a) Location: Office a) Employee use and handle hazardous chemicals such as but not limited to adhesive, (Toluene and Methyl Ethyl Ketone) and wood dust( combustible dust) in the manufacturing of furniture.The employer did not provide information or training on hazardous chemicals; on or about 2/20/18.
Recent events (3)
- — F (S) $0
- — C (S) $0
- — Z (S) $0
More inspections at Urban Interiors Management INC
View Urban Interiors Management INC's full OSHA safety record →
More inspections in this industry (NAICS 238350)
More inspections in NY
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 343787388.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.