LITTLE ROCK, AR —
OSHA Inspection: E-Z SPUDS LLC
Foreign inspection · Safety discipline
At a glance
On , OSHA opened a foreign safety inspection of E-Z SPUDS LLC in 24501 BRANDON LANE, LITTLE ROCK, AR 72223 (NAICS 311991). OSHA activity number 343797767.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- E-Z SPUDS LLC
- Site address
- 24501 BRANDON LANE
- City
- LITTLE ROCK
- State
- AR
- ZIP
- 72223
- Mailing
- 24501 BRANDON LANE, LITTLE ROCK, AR 72223
What kind of inspection was it?
- Inspection type
- Foreign (L)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 311991
- Employees
- 2
- Ownership type
- A
Citations
10 citations on file for this inspection.
1910.219 F03
- Issued
- Jun 19, 2019
- Abate by
- Jul 11, 2019
- Penalty
- Initial $3,978 · Current $3,978
General-duty citation text
29 CFR 1910.219(f)(3): Sprocket wheels and chains which were seven -7 feet or less above floors or platforms were not enclosed: (a) On or about February 14, 2019, and at times thereto, in the food prep area, where employees used a conveyor, which lacked guarding.
Recent events (1)
- — Z (S) $3978
1910.303 G02 II
- Issued
- Jun 19, 2019
- Abate by
- Jul 18, 2019
- Penalty
- Initial $3,978 · Current $3,978
General-duty citation text
29 CFR 1910.303(g)(2)(ii): In locations where electric equipment was likely to be exposed to physical damage, enclosures or guards were not so arranged and of such strength as to prevent such damage: On or about February 21, 2019, and at times prior thereto, in the food prep area, the employer failed to replace corroded electric metallic tube conduits, which had exposed conductors e.g. wires.
Recent events (1)
- — Z (S) $3978
1910.305 B01 I
- Issued
- Jun 19, 2019
- Abate by
- Jul 18, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(1)(i): Openings through which conductors entered cutout boxes, cabinets, or fittings were not effectively closed: (a) On or about February 21, 2019, and at times prior thereto, in the food prep area, the employer did not ensure unused opening(s) on the Hubbell outlet box was effectively closed to guard against live parts.
Recent events (1)
- — Z (S) $0
1910.303 H02 III A
- Issued
- Jun 19, 2019
- Abate by
- Jul 18, 2019
- Penalty
- Initial $3,978 · Current $3,978
General-duty citation text
29 CFR 1910.303(h)(2)(iii)(A): The installations shall be made with metal-enclosed equipment or shall be enclosed in a vault or in an area to which access is controlled by a lock: (a) On or about February 21, 2019, and at times prior thereto, outdoors, where the cooling unit to refrigeration equipment with identified exposed live parts, lacked a metal-enclosure.
Recent events (1)
- — Z (S) $3978
1910.305 C04
- Issued
- Jun 19, 2019
- Abate by
- Jul 18, 2019
- Penalty
- Initial $3,978 · Current $3,978
General-duty citation text
29 CFR 1910.305(c)(4): Faceplates for flush-mounted snap switches. Snap switches mounted in boxes did not have faceplates installed so as to completely cover the opening and seat against the finished surface: (a) On or about February 21, 2019, and at times prior thereto, in the food prep area, the employer did not ensure that faceplates were installed to cover light switches. Instance a: Mounted to steel column. Instance b: Wall next to sliding glass office window.
Recent events (1)
- — Z (S) $3978
1910.305 G01 IV A
- Issued
- Jun 19, 2019
- Abate by
- Jul 18, 2019
- Penalty
- Initial $3,978 · Current $3,978
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: (a) On or about February 21, 2019, and at times prior thereto, in the food prep area, where the employer used receptacles to plug in overhead lamps as a substitute for fixed wiring.
Recent events (1)
- — Z (S) $3978
1910.305 G02 III
- Issued
- Jun 19, 2019
- Abate by
- Jul 18, 2019
- Penalty
- Initial $3,410 · Current $3,410
General-duty citation text
29 CFR 1910.305(g)(2)(iii): Flexible cords were not connected to devices and fittings so that tension would not be transmitted to joints or terminal screws: (a) On or about February 21, 2019, and at times prior thereto, in the food prep area, the employer did not ensure that strain relief was provided on a cable that was providing electrical current to an electric Hobart potato peeler.
Recent events (1)
- — Z (S) $3410
1910.305 J01 IV
- Issued
- Jun 19, 2019
- Abate by
- Jul 18, 2019
- Penalty
- Initial $3,978 · Current $3,978
General-duty citation text
29 CFR 1910.305(j)(1)(iv): Fixtures installed in wet or damp locations were not approved for the purpose and were not so constructed or installed that water could not enter or accumulate in wireways, lamp holders or other electrical parts: (a) On or about February 21, 2019, and at times prior thereto, in the food prep area, the employer did not ensure that outlets installed were approved for the wet location.
Recent events (1)
- — Z (S) $3978
1910.305 J02 IV
- Issued
- Jun 19, 2019
- Abate by
- Jul 18, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(j)(2)(iv): A receptacle installed in a wet or damp location was not suitable for the location: (a) On February 21, 2019, and at times prior thereto, in the food prep area, the employer did not ensure that receptacles installed were suitable for the location.
Recent events (1)
- — Z (S) $0
1910.305 J03 I
- Issued
- Jun 19, 2019
- Abate by
- Jul 18, 2019
- Penalty
- Initial $2,273 · Current $2,273
General-duty citation text
29 CFR 1910.305(j)(3)(i): Appliances had live parts normally exposed to employee contact: (a) On or about February 21, 2019, and at times prior thereto, in the food prep area, where the employer did not ensure that the Hobart potato peeler and the French fry cutter exposed live parts were covered.
Recent events (1)
- — Z (S) $2273
More inspections at E-Z Spuds LLC
View E-Z Spuds LLC's full OSHA safety record →
More inspections in this industry (NAICS 311991)
More inspections in AR
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 343797767.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.