On , OSHA opened a complaint health inspection of BAY TOWEL, INC. in 2580 S BROADWAY, GREEN BAY, WI 54304 (NAICS 812331). OSHA activity number 343800512.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- BAY TOWEL, INC.
- Site address
- 2580 S BROADWAY
- City
- GREEN BAY
- State
- WI
- ZIP
- 54304
- Mailing
- 2580 S BROADWAY, GREEN BAY, WI 54304
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 812331
- Employees
- 200
- Ownership type
- A
Citations
2 citations on file for this inspection.
1910.305 G01 IV A
- Issued
- Feb 25, 2019
- Penalty
- Initial $4,831 · Current $3,382 Reduced
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and cables may not be used as a substitute for the fixed wiring of a structure: At a facility located at 2580 S. Broadway, Green Bay, WI 54304; flexible cords used to power hanging electrical outlet pendants in the Mending areas were used as a substitute for fixed wiring of a structure when the flexible cords were zip tied to the metal conduit above the Mending work stations.
Recent events (2)
- · I (S) $3381.7
- · Z (S) $4831
1910.305 G02 III
- Issued
- Feb 25, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables shall be connected to devices and fittings so that strain relief is provided that will prevent pull from being directly transmitted to joints or terminal screws. At a facility located at 2580 S. Broadway, Green Bay, WI 54304; flexible cords used to power hanging electrical outlet pendants in the Mending areas were not connected to devices and fitting so that strain relief was provided.