JOINT BASE LEWIS MCCHORD, WA ·
OSHA Inspection: ARMY & AIR FORCE EXCHANGE SERVICE
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of ARMY & AIR FORCE EXCHANGE SERVICE in BUILDING 5280 PENDLETON AVENUE, JOINT BASE LEWIS MCCHORD, WA 98433 (NAICS 452112). OSHA activity number 343802328.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- ARMY & AIR FORCE EXCHANGE SERVICE
- Site address
- BUILDING 5280 PENDLETON AVENUE
- City
- JOINT BASE LEWIS MCCHORD
- State
- WA
- ZIP
- 98433
- Mailing
- BUILDING 5280 PENDLETON AVENUE MAILSTOP 46, JOINT BASE LEWIS MCCHORD, WA 98433
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Non-union (B)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 452112
- Employees
- 187
- Ownership type
- Federal government (D)
Citations
6 citations on file for this inspection.
1910.303 B02
- Issued
- Mar 12, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: (a) OPS Room; A Hamilton Beach Flex brew electric kettle/ coffee pot, electric air freshener, and black charger were plugged into a surge protector power strip (relocatable power tap). The UL listing states that relocatable power taps are designed for low amperage computer and audiovisual types of equipment, and not appliances. This exposes employees to possible electrical fire hazards.
Recent events (1)
- · Z (S) $0
1910.305 B01 II
- Issued
- Mar 12, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed: a) Electronics Storeroom; Breaker #32 was missing a blank or breaker. This exposes employees to potential electrical shock hazards.
Recent events (1)
- · Z (S) $0
1910.37 A03
- Issued
- Mar 12, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(a)(3): Exit routes were not kept free and unobstructed. Materials or equipment were placed, either permanently or temporarily, within the exit route: a) MPA/ Warehouse emergency exit door adjacent to employee parking lot; A mannequin, metal cart on wheels, and cardboard boxes were stored adjacent to the exit discharge door for the area. b) Loading Dock exit discharge door; A floor washer, a floor buffer and plastic yellow caution wet floor signs were stored in the exit route.
Recent events (1)
- · Z (O) $0
1910.159 C10
- Issued
- Mar 12, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.159(c)(10): The minimum vertical clearance of 18 inches between automatic sprinkler systems sprinklers and the material below was not maintained: a) OPS Room; Posters were stored within approximately 1-2 inches from the sprinkler head. This exposes employees to potential smoke inhalation hazards.
Recent events (1)
- · Z (O) $0
1910.303 G01 II
- Issued
- Mar 12, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage: a) Stockroom Foremans Office; A metal file cabinet and boxes of scan handles were stored underneath breaker panel 2F4.
Recent events (1)
- · Z (O) $0
1910.305 G01 I
- Issued
- Mar 12, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(i): Flexible cords and cables were not approved for conditions of use and location: a) OPS Room; A Simply perfect microwave and Idea refrigerator were plugged into a heavy duty three prong extension cord for over 90 days. This exposes employees to potential electrical hazards.
Recent events (1)
- · Z (O) $0
More inspections at Army & AIR Force Exchange Service
View Army & AIR Force Exchange Service's full OSHA safety record →
More inspections in this industry (NAICS 452112)
More inspections in WA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 343802328.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.