OSHA Inspection: CONSUMER'S BEVERAGES, INC
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of CONSUMER'S BEVERAGES, INC in 2205 GEORGE URBAN BOULEVARD, DEPEW, NY 14043 (NAICS 236220). OSHA activity number 343825709.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- CONSUMER'S BEVERAGES, INC
- Site address
- 2205 GEORGE URBAN BOULEVARD
- City
- DEPEW
- State
- NY
- ZIP
- 14043
- Mailing
- 2230 SOUTH PARK AVENUE, BUFFALO, NY 14220
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Non-union (B)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 236220
- Employees
- 5
- Ownership type
- Private (A)
Citations
2 citations on file for this inspection.
1926.405 B01
- Issued
- May 10, 2019
- Penalty
- Initial $3,695 · Current $1,900 Reduced
General-duty citation text
29 CFR 1926.405(b)(1): Unused openings in cabinets, boxes, and fittings were not effectively closed: a) On or about 3/5/19, at the electric panel area of the site, Depew, NY. The panel, of 120/204 Volt, 200 Amp, had 3 unused openings at the sides of panel not effectively closed. In addition, conductors did not enter the panel through openings that resulted in conductors being pinched between panel and cover, not protected from abrasion. NO ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
- · I (S) $1900
- · Z (S) $3695
1926.403 H
- Issued
- May 10, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1926.403(h): Each service, feeder, and branch circuit was not legibly marked at its disconnecting means or overcurrent device to indicate its purpose, nor located and arranged so that the purpose was evident: a) On or about 3/5/19, at the electric panel of the site, Depew, NY. The panel of 120/204 V, 200 Amp was not provided with a directory for the breakers. NO ABATEMENT CERTIFICATION REQUIRED