COLORADO SPRINGS, CO ·
OSHA Inspection: RHODESCO, INC
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of RHODESCO, INC in 3910 SINTON ROAD, COLORADO SPRINGS, CO 80907 (NAICS 323114). OSHA activity number 343826277.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- RHODESCO, INC
- Site address
- 3910 SINTON ROAD
- City
- COLORADO SPRINGS
- State
- CO
- ZIP
- 80907
- Mailing
- 3910 SINTON ROAD, COLORADO SPRINGS, CO 80907
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Non-union (B)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 323114
- Employees
- 15
- Ownership type
- Private (A)
Citations
1 citation on file for this inspection.
1910.304 B04 II
- Issued
- Mar 11, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.304(b)(4)(ii): Receptacle outlets did not comply with the following provision: where connected to a branch circuit supplying two or more receptacles or outlets, a receptacle may not supply a total cord-and plug-connected load in excess of the maximum specified in Table S-4: a) Xerox 4112: On or about February 27, 2019, and at times prior, a potential electrical hazard was present where a re-locatable power tap rated at 15 amperes with six receptacles was powering a paper feeder rated at 12 amps, a desktop computer rated at 2.17 amps, and a monitor rated at 0.56 amps. Note: Amps total is 14.73 (max), which is greater than the 12 amps allowed by Table S-4 and .35 amps lower than the listed capacity of the outlet device.
Recent events (2)
- · I (O) $0
- · Z (O) $0
More inspections in this industry (NAICS 323114)