OSHA Inspection: U.S. DEPARTMENT OF AGRICULTURE AGRICULTURAL RESEARCH SERVICE USDA ARS

Planned inspection · Health discipline

On , OSHA opened a planned health inspection of U.S. DEPARTMENT OF AGRICULTURE AGRICULTURAL RESEARCH SERVICE USDA ARS in 275 SOUTH RUSSEL STREET, WEST LAFAYETTE, IN 47907 (NAICS 924120). OSHA activity number 343850475.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch U.S. Department of Agriculture Agricultural Research Service Usda ARS for free Get an email when a new federal OSHA severe-injury report for U.S. Department of Agriculture Agricultural Research Service Usda ARS is published. One employer, no account, unsubscribe in one click.
Site address
275 SOUTH RUSSEL STREET
City
WEST LAFAYETTE
State
IN
ZIP
47907
Mailing
275 SOUTH RUSSEL STREET, WEST LAFAYETTE, IN 47907
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Health
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
924120
Employees
50
Ownership type
Federal government (D)

2 citations on file for this inspection.

1910.303 B02

Serious Gravity 5 3 instances 3 exposed
Issued
Aug 9, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2) as required by 1960.8(b): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:  (a) On or about March 14, 2019 in room 148, the soil digestion lab, a relocatable power tap, which was UL listed under 31F8 and TVSS, had been used on a wet towel and powered a vortex and magnetic stir plate.  (b) On or about March 14, 2019 in the hydraulic lab by the sink on the floor, two relocatable power taps, which were UL listed under 31F8 and TVSS, had been used to power an experiment involving running water. The concrete around one power tap showed evidence of having been wet.
Recent events (1)
  • · Z (S) $0

1910.303 B06

Serious Gravity 1 2 instances 2 exposed
Issued
Aug 9, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(6): Conductors or equipment were located in damp or wet locations; where exposed to gases, fumes, vapors, liquids, or other agents that had a deteriorating effect on the conductors or equipment; or where exposed to excessive temperatures and were not identified for use in the operating environment:  (a) On or about March 14, 2019 in room 148, the soil digestion lab, the employer had failed to inspect and provide equipment for use that had not been corroded from acidic fumes and liquids. The Vortex Genie 2 from Scientific Industries, Model G560, SN#2492658, and the Magnetic Stir Plate from Fisher Scientific, SN#902N0180 were used by employees and the equipment was corroded.