POLO, IL —
OSHA Inspection: XENA INTERNATIONAL, INC.
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of XENA INTERNATIONAL, INC. in 910 S. DIVISION AVENUE, POLO, IL 61064 (NAICS 424690). OSHA activity number 343864229.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- XENA INTERNATIONAL, INC.
- Site address
- 910 S. DIVISION AVENUE
- City
- POLO
- State
- IL
- ZIP
- 61064
- Mailing
- 910 S. DIVISION AVENUE, POLO, IL 61064
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 424690
- Employees
- 25
- Ownership type
- A
Citations
6 citations on file for this inspection.
1910.36 D02
- Issued
- May 22, 2019
- Abate by
- Jul 12, 2019
- Penalty
- Initial $3,031 · Current $1,950 Reduced
General-duty citation text
29 CFR 1910.36(d)(2): Exit route doors were operated by a device or alarm that could restrict emergency use of the exit route if the device or alarm fails. On or about March 15, 2019, and after the exit in the warehouse was restricted with a fence that required a key code to enter through the gate to the emergency exit. Employees are exposed to life safety hazards due to the restricted exit. Abatement certification is required for this item in accordance with the requirements of 29 CFR 1903.19(c).
Recent events (2)
- — I (S) $1950
- — Z (S) $3031
1910.134 C01
- Issued
- May 22, 2019
- Abate by
- Aug 1, 2019
- Penalty
- Initial $5,304 · Current $3,450 Reduced
General-duty citation text
29 CFR 1910.134(c)(1): Where employee use of respiratory protection is required, the employer must develop and implement a written respiratory protection program that includes the provisions in 29 CFR 1910.134(c)(1)(i)-(ix). On or about March 15, 2019, employees were exposed to respiratory stressors while being required to wear a 3M full face respirator when conducting mixing operations and handling chemicals. The employer did not develop and implement a written respiratory program that included medical evaluations, fit testing, and training. Abatement documentation is required for this item in accordance with the requirements of 29 CFR 1903.19(d).
Recent events (2)
- — I (S) $3450
- — Z (S) $5304
1910.303 B07 I
- Issued
- May 22, 2019
- Penalty
- Initial $3,031 · Current $1,950 Reduced
General-duty citation text
29 CFR 1910.303(b)(7)(i): Unused openings in boxes, raceways, auxiliary gutters, cabinets, equipment cases, or housings were not effectively closed to afford protection substantially equivalent to the wall of the equipment. On or about March 15, 2019 the employer failed to close unused openings in a control panel located in the control room exposing employees to electrical shock hazards. No abatement or certification is due for this item.
Recent events (2)
- — I (S) $1950
- — Z (S) $3031
1910.303 G01
- Issued
- May 22, 2019
- Abate by
- Jun 13, 2019
- Penalty
- Initial $2,273 · Current $1,450 Reduced
General-duty citation text
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment: On or about March 15, 2019 access to electrical panels were obstructed by a forklift preventing personnel from shutting down the source of power in the event of an emergency or accident in the facility. Abatement certification is required for this item in accordance with the requirements of 29 CFR 1903.19(c).
Recent events (2)
- — I (S) $1450
- — Z (S) $2273
1910.333 B02 I
- Issued
- May 22, 2019
- Abate by
- Jun 20, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.333(b)(2)(i): The employer did not make a written copy of the procedures outlined in paragraph (b)(2) of 29 CFR 1910.333 available for inspection by employees and by the Assistant Secretary of Labor and his or her authorized representatives: On or about January 18, 2019 an employee installed a new GFCI outlet and the employer did not have a copy of the written procedures available for inspection. Abatement certification is required for this item in accordance with the requirements of 29 CFR 1903.19(c).
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.1200 E01
- Issued
- May 22, 2019
- Abate by
- Jun 20, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.1200(e)(1): The employer did not develop, implement, and/or maintain at the workplace a written hazard communication program. On or about March 15, 2019 the employer did not implement and maintain a written hazard communication program at the workplace. Employees handle chemicals such as citric acid, potassium acetate, calcium chloride, potassium phosphate, sodium carbonate, and sodium benzoate. Abatement documentation is required for this item in accordance with the requirements of 29 CFR 1903.19(d).
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Xena International, INC.
View Xena International, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 424690)
More inspections in IL
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 343864229.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.