APOPKA, FL ·
OSHA Inspection: FL SEAMLESS GUTTERS LLC
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of FL SEAMLESS GUTTERS LLC in 2632 PEMBERTON DRIVE #103, APOPKA, FL 32703 (NAICS 238170). OSHA activity number 343911483.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- FL SEAMLESS GUTTERS LLC
- Site address
- 2632 PEMBERTON DRIVE #103
- City
- APOPKA
- State
- FL
- ZIP
- 32703
- Mailing
- 2632 PEMBERTON DRIVE #103, APOPKA, FL 32703
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 238170
- Employees
- 3
- Ownership type
- A
Citations
4 citations on file for this inspection.
1910.36 G02
- Issued
- Aug 28, 2019
- Penalty
- Initial $2,273 · Current $2,273
General-duty citation text
29 CFR 1910.36(g)(2): Exit access(es) were not at least 28 inches (71.1 cm) wide at all points: a. On or about 4/5/19, at the jobsite, in the work shop area, employees were exposed to entrapment hazards, in that, the rear exit door and exit route was blocked.
Recent events (1)
- · Z (S) $2273
1910.303 F02
- Issued
- Aug 28, 2019
- Abate by
- Sep 17, 2019
- Penalty
- Initial $1,705 · Current $1,705
General-duty citation text
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident: a. On or about 4/5/19, at the jobsite, employees were exposed to electrical shock and burn hazards, in that, the electrical breakers in the breaker panel were not labeled.
Recent events (1)
- · Z (S) $1705
1910.305 B01 II
- Issued
- Aug 28, 2019
- Abate by
- Sep 17, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed: a. On or about 4/5/19, at the jobsite, employees were exposed to electrical shock and burn hazards, in that, there were openings in the breaker panel that were covered with tape.
Recent events (1)
- · Z (S) $0
1910.303 G01 I
- Issued
- Aug 28, 2019
- Abate by
- Sep 10, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(1)(i): Work space was less than 30 inches wide in front of electric equipment operating at 600 volts, nominal, or less: a. On or about 4/5/19, at the jobsite, in the shop area, materials were stored within 15 inches of the front of the breaker panel door.
Recent events (1)
- · Z (O) $0
More inspections in this industry (NAICS 238170)
More inspections in FL
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 343911483.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.