Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,193,745Inspections Most recent open 2026-08-06 Last loaded 2026-08-10

OSHA Inspection: FL SEAMLESS GUTTERS LLC

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of FL SEAMLESS GUTTERS LLC in 2632 PEMBERTON DRIVE #103, APOPKA, FL 32703 (NAICS 238170). OSHA activity number 343911483.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch FL Seamless Gutters LLC for free Get an email when a new federal OSHA severe-injury report for FL Seamless Gutters LLC is published. One employer, no account, unsubscribe in one click.
Site address
2632 PEMBERTON DRIVE #103
City
APOPKA
State
FL
ZIP
32703
Mailing
2632 PEMBERTON DRIVE #103, APOPKA, FL 32703
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238170
Employees
3
Ownership type
A

4 citations on file for this inspection.

1910.36 G02

Serious Gravity 5 1 instance 3 exposed
Issued
Aug 28, 2019
Penalty
Initial $2,273 · Current $2,273
29 CFR 1910.36(g)(2): Exit access(es) were not at least 28 inches (71.1 cm) wide at all points:  a.  On or about 4/5/19, at the jobsite, in the work shop area, employees were exposed to entrapment hazards, in that, the rear exit door and exit route was blocked.
Recent events (1)
  • · Z (S) $2273

1910.303 F02

Serious Gravity 1 1 instance 3 exposed
Issued
Aug 28, 2019
Abate by
Sep 17, 2019
Penalty
Initial $1,705 · Current $1,705
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident:  a.  On or about 4/5/19, at the jobsite, employees were exposed to electrical shock and burn hazards, in that, the electrical breakers in the breaker panel were not labeled.
Recent events (1)
  • · Z (S) $1705

1910.305 B01 II

Serious Gravity 5 1 instance 3 exposed
Issued
Aug 28, 2019
Abate by
Sep 17, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed:   a.  On or about 4/5/19, at the jobsite, employees were exposed to electrical shock and burn hazards, in that, there were openings in the breaker panel that were covered with tape.
Recent events (1)
  • · Z (S) $0

1910.303 G01 I

Other-than-serious 1 instance 3 exposed
Issued
Aug 28, 2019
Abate by
Sep 10, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(1)(i): Work space was less than 30 inches wide in front of electric equipment operating at 600 volts, nominal, or less:  a. On or about 4/5/19, at the jobsite, in the shop area, materials were stored within 15 inches of the front of the breaker panel door.
Recent events (1)
  • · Z (O) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 343911483.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.