Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,191,871Inspections Most recent open 2026-07-30 Last loaded 2026-08-03

OSHA Inspection: SUPERIOR TASKING ADVANTAGE CONTRACTING, INC.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of SUPERIOR TASKING ADVANTAGE CONTRACTING, INC. in 7331 9TH CALVARY REGIMENT ROAD, FORT KNOX, KY 40121 (NAICS 561730). OSHA activity number 343913976.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Superior Tasking Advantage Contracting, INC. for free Get an email when a new federal OSHA severe-injury report for Superior Tasking Advantage Contracting, INC. is published. One employer, no account, unsubscribe in one click.
Site address
7331 9TH CALVARY REGIMENT ROAD
City
FORT KNOX
State
KY
ZIP
40121
Mailing
4704 ALLSTAR COURT, RALEIGH, NC 27612
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
561730
Employees
44
Ownership type
A

8 citations on file for this inspection.

1910.212 A05

Serious Gravity 5 1 instance 1 exposed
Issued
Sep 25, 2019
Penalty
Initial $6,630 · Current $3,000 Reduced
29 CFR 1910.212(a)(5): Exposure of blades. When the periphery of the blades of a fan is less than seven (7) feet above the floor or working level, the blades were not guarded.     a) Fort Knox Army Installation - Maintenance Shop located at 7331 9th Cavalry Regt. Rd., Fort Knox, KY:  On or about April 3, 2019, the center cap of the pedestal fan was missing creating an opening of 3.5 inches exposing the blades.
Recent events (2)
  • · I (S) $3000
  • · Z (S) $6630

1910.242 B

Serious Gravity 5 1 instance 1 exposed
Issued
Sep 25, 2019
Penalty
Initial $6,630 · Current $4,000 Reduced
29 CFR 1910.242(b): Compressed air was used for cleaning purposes but was not reduced to less than 30 p.s.i.:    a) Fort Knox Army Installation - Maintenance Shop located at 7331 9th Cavalry Regt. Rd., Fort Knox, KY:  On or about April 3, 2019, the compressor wand used primarily to blow debris from mowers had a tip pressure of 74 p.s.i.
Recent events (2)
  • · I (S) $4000
  • · Z (S) $6630

1910.304 G05

Serious Gravity 5 1 instance 1 exposed
Issued
Sep 25, 2019
Penalty
Initial $5,304 · Current $3,000 Reduced
29 CFR 1910.304(g)(5): Grounding path. The path to ground from circuits, equipment, and enclosures was not  permanent, continuous, and effective.    a) Fort Knox Army Installation - Maintenance Shop located at 7331 9th Cavalry Regt. Rd., Fort Knox, KY:  On or about April 3, 2019, The electrical power cord to the Husky Pro Air Compressor was missing the ground pin resulting in the equipment being ungrounded exposing workers to electric shock.
Recent events (2)
  • · I (S) $3000
  • · Z (S) $5304

1910.37 A03

Other-than-serious 1 instance 1 exposed
Issued
Sep 25, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.37(a)(3): Exit routes were not free and unobstructed.  a) Fort Knox Army Installation - Maintenance Shop located at 7331 9th Cavalry Regt. Rd., Fort Knox, KY:  On or about April 3, 2019, the exit door inside of the shop was blocked with a backpack blower and pedestal floor fan.
Recent events (2)
  • · I (O) $0
  • · Z (O) $0

1910.37 B02

Other-than-serious 1 instance 1 exposed
Issued
Sep 25, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(2): Each exit was not clearly visible and marked by a sign reading "Exit."  a) Fort Knox Army Installation - Maintenance Shop located at 7331 9th Cavalry Regt. Rd., Fort Knox, KY:  On or about April 3, 2019, the exit was not marked as an "EXIT".
Recent events (2)
  • · I (O) $0
  • · Z (O) $0

1910.157 E01

Other-than-serious 1 instance 1 exposed
Issued
Sep 25, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.157(e)(1): The employer did not perform inspection, maintenance and testing of all portable fire extinguishers in the workplace:  a)  Fort Knox Army Installation - Maintenance Shop located at 7331 9th Cavalry Regt. Rd., Fort Knox, KY:  On or about April 3, 2019, the fire extinguisher was not inspected and maintained.
Recent events (2)
  • · I (O) $0
  • · Z (O) $0

1910.303 F02

Other-than-serious 1 instance 1 exposed
Issued
Sep 25, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, unless located and arranged so the purpose is evident:  a) Fort Knox Army Installation - Maintenance Shop located at 7331 9th Cavalry Regt. Rd., Fort Knox, KY:  On or about April 3, 2019, four of the five breakers in the 110V electrical panel box was not properly labeled.
Recent events (2)
  • · I (O) $0
  • · Z (O) $0

1910.305 A02 X

Other-than-serious 1 instance 1 exposed
Issued
Sep 25, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.305(a)(2)(x): Cables were not protected from accidental damage, as might be caused, for example, by sharp corners, projections, and doorways or other pinch points.  a) Fort Knox Army Installation - Maintenance Shop located at 7331 9th Cavalry Regt. Rd., Fort Knox, KY:  On or about April 3, 2019, the protective cover for the electrical cord on the base of the pedestal floor fan was missing exposing the cord to the metal edge of the base.
Recent events (2)
  • · I (O) $0
  • · Z (O) $0

View Superior Tasking Advantage Contracting, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 343913976.