Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,194,531Inspections Most recent open 2026-08-11 Last loaded 2026-08-14

OSHA Inspection: ARMY AND AIR FORCE EXCHANGE SERVICE - MILITARY CLOTHING

Planned inspection · Health discipline

On , OSHA opened a planned health inspection of ARMY AND AIR FORCE EXCHANGE SERVICE - MILITARY CLOTHING in 1431 MAHONE AVE. BUILDING 9025, FORT LEE, VA 23801 (NAICS 448190). OSHA activity number 343942140.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Army and AIR Force Exchange Service - Military Clothing for free Get an email when a new federal OSHA severe-injury report for Army and AIR Force Exchange Service - Military Clothing is published. One employer, no account, unsubscribe in one click.
Site address
1431 MAHONE AVE. BUILDING 9025
City
FORT LEE
State
VA
ZIP
23801
Mailing
1431 MAHONE AVE., BLDG 9025 ATTN: GERALDINE BROWN, FORT LEE, VA 23801
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Health
Advance notice
No
Union status
Non-union (B)
Opened
Case closed
Last modified
Data loaded
NAICS code
448190
Employees
13
Ownership type
Federal government (D)

4 citations on file for this inspection.

1910.303 B07 I

Serious Gravity 5 1 instance 13 exposed
Issued
Jul 22, 2019
Abate by
Aug 15, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(7)(i): Unused openings in boxes, raceways, auxiliary gutters, cabinets, equipment cases, or housings were not effectively closed to afford protection substantially equivalent to the wall of the equipment:  a) 1431 Mahone Ave., Bldg 9025, Fort Lee, VA 23801: On or about April 18, 2019, and times prior thereto, unused openings in a panel marked PA in a common hallway through a Military Clothing stock area, had knockouts missing in two locations, exposing employees to electrical hazards.  Abatement certification required within 10 days after abatement date. The certification shall include a statement that abatement is complete, the date and method of abatement, and state that employees and their representatives were informed of this abatement.
Recent events (1)
  • · Z (S) $0

1910.303 G02 I

Serious Gravity 5 1 instance 13 exposed
Issued
Jul 22, 2019
Abate by
Aug 15, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i):  a) 1431 Mahone Ave., Bldg 9025, Fort Lee, VA 23801: On or about April 18, 2019, and times prior thereto, a panel marked PA in a common hallway through a Military Clothing stock area, had a panel door that remained ajar due to a missing door lock that rendered the panel unguarded, exposing employees to electrical hazards.  Abatement certification required within 10 days after abatement date. The certification shall include a statement that abatement is complete, the date and method of abatement, and state that employees and their representatives were informed of this abatement.
Recent events (1)
  • · Z (S) $0

1910.304 F01 VIII

Serious Gravity 5 2 instances 13 exposed
Issued
Jul 22, 2019
Abate by
Aug 15, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.304(f)(1)(viii): Circuit breakers used as switches in 120-volt and 277-volt, fluorescent lighting circuits were not listed and marked "SWD":  a) 1431 Mahone Ave., Bldg 9025, Fort Lee, VA 23801: On or about April 18, 2019, and times prior thereto, employees were required to turn fluorescent lights on in the morning and off in the evening using circuit breakers that were not listed and marked "SWD" in two panel boxes, exposing employees to electrical hazards.  Abatement certification required within 10 days after abatement date. The certification shall include a statement that abatement is complete, date and method of abatement, and states employees and their representatives were informed of this abatement.
Recent events (1)
  • · Z (S) $0

1904.32 B02 II

Other-than-serious 1 instance 13 exposed
Issued
Jul 22, 2019
Abate by
Aug 15, 2019
Penalty
Initial $0 · Current $0
29 CFR 1904.32(b)(2)(ii): The annual summary did not include one or more of the following elements: the calendar year covered, the company's name, establishment name, establishment address, annual average number of employees covered by the OSHA 300 Log, and the total hours worked by all employees covered by the OSHA 300 Log:  a) 1431 Mahone Ave., Bldg 9025, Fort Lee, VA 23801: The employer combined the recordable injuries and illnesses on the OSHA 300A Summary log or equivalent form, from multiple stores on Fort Lee with the Military Clothing establishment, and did not record the number of employees and total hours worked at the establishment.  Abatement certification required within 10 days after abatement date. The certification shall include a statement that abatement is complete, date and method of abatement, and states employees and their representatives were informed of this abatement.
Recent events (1)
  • · Z (O) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 343942140.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.