MINOOKA, IL ·
OSHA Inspection: UNITED STATES COLD STORAGE, INC.
Complaint inspection · Health discipline
At a glance
On , OSHA opened a complaint health inspection of UNITED STATES COLD STORAGE, INC. in 601 TWIN RAIL DR., MINOOKA, IL 60447 (NAICS 493120). OSHA activity number 343978581.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- UNITED STATES COLD STORAGE, INC.
- Site address
- 601 TWIN RAIL DR.
- City
- MINOOKA
- State
- IL
- ZIP
- 60447
- Mailing
- 601 TWIN RAIL DR., MINOOKA, IL 60447
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Complete (A)
- Discipline
- Health
- Advance notice
- No
- Union status
- Non-union (B)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 493120
- Employees
- 180
- Ownership type
- Private (A)
Citations
1 citation on file for this inspection.
1910.119 D03 II
- Issued
- Sep 30, 2019
- Abate by
- Nov 20, 2019
- Penalty
- Initial $13,260 · Current $8,000 Reduced
0170
General-duty citation text
29 CFR 1910.119(d)(3)(ii): The employer did not document that equipment complies with recognized and generally accepted good engineering practices. On or about May 2, 2019, the employer failed to document that equipment complied with recognized and generally good engineering practices (RAGAGEP) for the following: a. The doors leading from areas such as, but not limited to, the Electrical Room, the Switch Gear 1 Room, and the Fire Pump/Rise Room 1 leading into Engine Room 1 were not tight-fitting (i.e., the design function of tight fitting doors to/from ammonia machine rooms is to act as part of the equipment system to provide a secondary containment for releases of ammonia from equipment in the engine room such that the ammonia does not migrate outside the engine room). The employer failed to document compliance with RAGAGEP such as, but not limited to, IIAR Standard 2 (2014) - Standard for Safe Design of Closed-Circuit Ammonia Refrigeration System, Section 6.10.2. This hazardous condition exposed employees to the hazard of inhalation and burns from ammonia vapors. Abatement documentation is required for this item in accordance with the requirements of 29 CFR 1903.19(d).
Recent events (2)
- · I (O) $8000
- · Z (S) $13260
More inspections at United States Cold Storage, INC.
View United States Cold Storage, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 493120)
More inspections in IL
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 343978581.