Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,196,991Inspections Most recent open 2026-08-24 Last loaded 2026-08-27

OSHA Inspection: R&B RESURFACE & REMODELING, LLC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of R&B RESURFACE & REMODELING, LLC. in LAKE HERITAGE CIR, ORLANDO, FL 32803 (NAICS 236118). OSHA activity number 343982294.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch R&B Resurface & Remodeling, LLC. for free Get an email when a new federal OSHA severe-injury report for R&B Resurface & Remodeling, LLC. is published. One employer, no account, unsubscribe in one click.
Site address
LAKE HERITAGE CIR
City
ORLANDO
State
FL
ZIP
32803
Mailing
1510 CHEYENNE RD, DALLAS, TX 75217
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
236118
Employees
5
Ownership type
Private (A)

7 citations on file for this inspection.

1926.403 A

Serious Gravity 10 1 instance 4 exposed
Issued
Oct 4, 2019
Penalty
Initial $3,978 · Current $3,978
29 CFR 1926.403(a): Electrical conductors and equipment were not approved:  a. On or about May 03, 2019, at 1968 Lake Heritage Circle, near building 6, employees were using power supplied from extension cords connecting a 3 outlet adapter through the use of alligator clamps. The alligator clamps were directly connected to a circuit breaker and ground bar. The use of a homemade 2 conductor with alligator clip type connectors were not an approved electrical device.
Recent events (1)
  • · Z (S) $3978

1926.403 B01

Serious Gravity 10 1 instance 4 exposed
Issued
Oct 4, 2019
Penalty
Initial $0 · Current $0
29 CFR 1926.403(b)(1): Employer did not ensure that electrical equipment is free from recognized hazards that are likely to cause death or serious physical harm to employees:  a.  On or about May 03, 2019, at 1968 Lake Heritage Circle, near building 6, employees were using power supplied from extension cords connecting a 3 outlet adapter through the use of alligator clamps. The alligator clamps were connected hot to hot and neutral to ground. There was no neutral path to complete the circuit.
Recent events (1)
  • · Z (S) $0

1926.403 I02 I

Serious Gravity 10 1 instance 4 exposed
Issued
Oct 4, 2019
Penalty
Initial $0 · Current $0
29 CFR 1926.403(i)(2)(i): Live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by cabinets or other forms of enclosures, nor by any of the means listed in subparagraphs (A) through (D) of this paragraph:   a.  On or about May 03, 2019, at 1968 Lake Heritage Circle, near building 6, employees had to reach inside an energized breaker panel to install alligator type clips onto energized conductors.
Recent events (1)
  • · Z (S) $0

1926.404 B01 II

Serious Gravity 10 1 instance 4 exposed
Issued
Oct 4, 2019
Penalty
Initial $0 · Current $0
29 CFR 1926.404(b)(1)(ii): 1926.404(b)(1)(i): At this job site, the extension cords, being used to provide temporary power to energize portable power tools, were not protected with a ground fault circuit interrupter as specified in paragraph (b)(1)(ii) of this section, or an assured equipment grounding conductor program as specified in paragraph (b)(1)(iii) of this section to protect employees from electrical shock hazards on this construction site:  a. On or about May 03, 2019, at 1968 Lake Heritage Circle, near building 6, employees were using power supplied from extension cords connecting a 3 outlet adapter through the use of alligator clamps and the alligator clamps were directly connected to a circuit breaker and ground bar. There was no ground fault circuit interrupter between the breaker panel, extension cord, and the hand tools being used.
Recent events (1)
  • · Z (S) $0

1926.404 F06

Serious Gravity 10 1 instance 4 exposed
Issued
Oct 4, 2019
Penalty
Initial $0 · Current $0
29 CFR 1926.404(f)(6): The path to ground from circuits, equipment, or enclosures was not permanent and continuous:  a.  On or about May 03, 2019, at 1968 Lake Heritage Circle, near building 6, employees were using power supplied from extension cords connecting a 3 outlet adapter through the use of alligator clamps. There was no ground connection from the outlet adapter to the breaker panel.
Recent events (1)
  • · Z (S) $0

1926.403 B01 III

Other-than-serious 1 instance 4 exposed
Issued
Oct 4, 2019
Penalty
Initial $319 · Current $319
29 CFR 1926.403(b)(1)(iii): The employer shall ensure that electrical equipment is free from recognized hazards that are likely to cause death or serious physical harm to employees. Safety of equipment shall be determined on the basis of the following considerations:  (a)  On or about May 03, 2019, at 1968 Lake Heritage Circle, near building 6, the employer did not ensure that electrical equipment was free from recognized hazards that were likely to cause death or serious physical harm to employees. Employees were using power supplied from extension cords that had not been inspected for damage prior to use.
Recent events (1)
  • · Z (O) $319

1926.403 B02

Other-than-serious 1 instance 4 exposed
Issued
Oct 4, 2019
Penalty
Initial $319 · Current $319
29 CFR 1926.403(b)(2): Listed, labeled, or certified equipment was not installed and used in accordance with instructions included in the listing, labeling, or certification:  a.  On or about May 03, 2019, at 1968 Lake Heritage Circle in Orlando, FL near building 6, employees were using power supplied from extension cords that were connected to an outdoor breaker panel using alligator clips and the breakers themselves were not labeled to identify their purpose.
Recent events (1)
  • · Z (O) $319

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 343982294.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.