ELMHURST, IL —
OSHA Inspection: IMOTORSPORTS INC.
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of IMOTORSPORTS INC. in 334 W. GRAND AVE., ELMHURST, IL 60126 (NAICS 441228). OSHA activity number 344016175.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- IMOTORSPORTS INC.
- Site address
- 334 W. GRAND AVE.
- City
- ELMHURST
- State
- IL
- ZIP
- 60126
- Mailing
- 334 W. GRAND AVE., ELMHURST, IL 60126
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 441228
- Employees
- 26
- Ownership type
- A
Citations
2 citations on file for this inspection.
1910.305 B01 II
- Issued
- Nov 14, 2019
- Penalty
- Initial $6,631 · Current $3,979 Reduced
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed: Service Area, D-1 Circuit Breaker Panel. On or about May 16, 2019, an unused opening in the 120/208v energized circuit breaker box was not covered, exposing employees to electrical shock and burns. There is no abatement documentation or certification required for this item.
Recent events (2)
- — I (S) $3979
- — Z (S) $6631
1910.303 G01
- Issued
- Nov 14, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment: Service Area. On or about May 16, 2019, the employer did not maintain at least 36 inches of space in front of 277v/480v motor control panels, circuit breaker panels and transformers. Access to working space in front of the panels for servicing and emergency shutoff was restricted by shop equipment, motorcycle parts, boxes of product and a large hanging banner. Employees working in the area or walking through were exposed to fire and electrical hazards. There is no abatement documentation or certification required for this item.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Imotorsports INC.
View Imotorsports INC.'s full OSHA safety record →
More inspections in this industry (NAICS 441228)
More inspections in IL
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 344016175.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.