Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: IMOTORSPORTS INC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of IMOTORSPORTS INC. in 334 W. GRAND AVE., ELMHURST, IL 60126 (NAICS 441228). OSHA activity number 344016175.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Imotorsports INC. — free Get an email when a new federal OSHA severe-injury report for Imotorsports INC. is published. One employer, no account, unsubscribe in one click.
Establishment
IMOTORSPORTS INC.
Site address
334 W. GRAND AVE.
City
ELMHURST
State
IL
ZIP
60126
Mailing
334 W. GRAND AVE., ELMHURST, IL 60126
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
441228
Employees
26
Ownership type
A

2 citations on file for this inspection.

1910.305 B01 II

Serious Gravity 5 1 instance 1 exposed
Issued
Nov 14, 2019
Penalty
Initial $6,631 · Current $3,979 Reduced
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed:    Service Area, D-1 Circuit Breaker Panel.  On or about May 16, 2019, an unused opening in the 120/208v energized circuit breaker box was not covered, exposing employees to electrical shock and burns.      There is no abatement documentation or certification required for this item.
Recent events (2)
  • — I (S) $3979
  • — Z (S) $6631

1910.303 G01

Other-than-serious 1 instance 6 exposed
Issued
Nov 14, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment:   Service Area.  On or about May 16, 2019, the employer did not maintain at least 36 inches of space in front of 277v/480v motor control panels, circuit breaker panels and transformers.  Access to working space in front of the panels for servicing and emergency shutoff was restricted by shop equipment, motorcycle parts, boxes of product and a large hanging banner.  Employees working in the area or walking through were exposed to fire and electrical hazards.   There is no abatement documentation or certification required for this item.