BEAUMONT, TX —
OSHA Inspection: HELENA LABORATORIES CORPORATION
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of HELENA LABORATORIES CORPORATION in 3795 WASHINGTON BLVD, BEAUMONT, TX 77705 (NAICS 339112). OSHA activity number 344027206.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- HELENA LABORATORIES CORPORATION
- Site address
- 3795 WASHINGTON BLVD
- City
- BEAUMONT
- State
- TX
- ZIP
- 77705
- Mailing
- 1530 LINDBERGH DRIVE, BEAUMONT, TX 77707
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 339112
- Employees
- 50
- Ownership type
- A
Citations
2 citations on file for this inspection.
1910.303 G01
- Issued
- Jul 9, 2019
- Abate by
- Jul 26, 2019
- Penalty
- Initial $4,262 · Current $2,557 Reduced
General-duty citation text
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment to permit ready and safe operation and maintenance of such equipment: a) On the north wall of the machine shop, equipment and material were less than 12 inches from several electrical safety switches, exposing employees to electrical hazards. b) On the south wall of the shipping and receiving department, a chemical barrel was less than 12 inches from an electrical panel, exposing employees to electrical hazards.
Recent events (2)
- — I (S) $2557.2
- — Z (S) $4262
1910.36 G02
- Issued
- Jul 9, 2019
- Abate by
- Jul 26, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.36(g)(2): Exit access was not at least 28 inches (71.1 cm) wide at all points: a) At the storage area, the exit access from the east exit door was not at least 28 inches wide, exposing employees to fire hazards.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections in this industry (NAICS 339112)