THORNE BAY, AK —
OSHA Inspection: U.S. FOREST SERVICE, THORNE BAY RANGER DISTRICT
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of U.S. FOREST SERVICE, THORNE BAY RANGER DISTRICT in 1312 FEDERAL WAY, THORNE BAY, AK 99919 (NAICS 924120). OSHA activity number 344032347.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- U.S. FOREST SERVICE, THORNE BAY RANGER DISTRICT
- Site address
- 1312 FEDERAL WAY
- City
- THORNE BAY
- State
- AK
- ZIP
- 99919
- Mailing
- 1312 FEDERAL WAY, THORNE BAY, AK 99919
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 924120
- Employees
- 61
- Ownership type
- D
Citations
21 citations on file for this inspection.
1910.106 D03 II
- Issued
- May 31, 2019
- Abate by
- Jul 3, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.106(d)(3)(ii): Flammable liquid storage cabinet(s) were not labeled in conspicuous lettering, "Flammable - Keep Fire Away". Warehouse yard area; on or about 21 May 2019 and times prior thereto; the employer did not ensure that warning labels were conspicuously posted on flammable storage cabinets. Two instances were noted: a. Fuel storage locker adjacent to paint locker; the fuel storage room did not have signage posted indicating flammables. b. Recreation conex area; the fuel storage conex did not have signage posted indicating flammables. The condition exposed employees to fire and explosion hazards.
Recent events (1)
- — Z (S) $0
1910.110 F02 I
- Issued
- May 31, 2019
- Abate by
- Jul 3, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.110(f)(2)(i): Containers in storage were not located so as to minimize exposure to excessive temperature rise, physical damage, or tampering by unauthorized persons. Warehouse yard area; on or about 21 May 2019 and times prior thereto; the employer did not ensure that propane fuel cylinders were stored in a manner to prevent damage. Three instances were noted where stored cylinders were not secured: a. Outside of paint locker area, ten propane cylinders of multiple quantities were not secured in a manner to prevent falling. Cylinders were stored free standing. b. Recreation shop conex number two, two 4BW240 propane cylinders were not secured in a manner to prevent falling. Cylinders were stored free standing. c. Recreation shop conex number one; one 4BW240 propane cylinder was not secured in a manner to prevent falling. Cylinder was stored free standing. This condition exposed employees to contact with flammable and combustible liquids and other fire hazards.
Recent events (1)
- — Z (S) $0
1910.212 B
- Issued
- May 31, 2019
- Abate by
- Jul 3, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.212(b): Machine(s) designed for fixed location(s) were not securely anchored to prevent walking or moving. Warehouse garage bay adjacent to compressor cage area; on or about 21 May 2019 and times prior thereto; the employer did not ensure that the Wilton Delta Drill Press, model 2704, serial number 137728, was securely mounted to prevent movement. This condition exposed employees to a struck by hazard.
Recent events (1)
- — Z (S) $0
1910.242 A
- Issued
- May 31, 2019
- Abate by
- Jul 3, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.242(a): Hand and portable powered tools or equipment were not kept in safe condition. Recreation Shop conex number two; on or about 21 May 2019 and times prior thereto; three instances were noted where hand tools were not kept in a safe working condition: a. A Pulaski had a cracked below the adze side of the wooden handle. b. A Pulaski had a cracked on the axe side of the wooden handle. c. A Sledgehammer had a crack on the fiberglass handle. This condition exposed employees to a struck by hazard.
Recent events (1)
- — Z (S) $0
1910.242 B
- Issued
- May 31, 2019
- Abate by
- Jul 3, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.242(b): Compressed air used for cleaning purposes was not reduced to less than 30 p.s.i. Warehouse garage bay; on or about 21 May 2019 and times prior thereto; an air nozzle employees use for cleaning purposes did not reduce air pressure to 30 p.s.i. or less. Shop air compressor was set at 120 p.s.i. This exposed employees to an air embolism and laceration hazards.
Recent events (1)
- — Z (S) $0
1910.253 B02 II
- Issued
- May 31, 2019
- Abate by
- Jul 3, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.253(b)(2)(ii): Inside of buildings, cylinders shall be stored in a well-protected, well-ventilated, dry location, at least 20 (6.1 m) feet from highly combustible materials such as oil or excelsior. Cylinders should be stored in definitely assigned places away from elevators, stairs, or gangways. Assigned storage spaces shall be located where cylinders will not be knocked over or damaged by passing or falling objects, or subject to tampering by unauthorized persons. Cylinders shall not be kept in unventilated enclosures such as lockers and cupboards. Garage bay adjacent to welding area; on or about 21 May 2019 and times prior thereto; the employer did not ensure that an oxygen cylinder used for welding was stored in a manner to prevent being knocked over or damaged. This condition exposed employees to a fire and explosion hazards.
Recent events (1)
- — Z (S) $0
1910.334 A02 II
- Issued
- May 31, 2019
- Abate by
- Jul 3, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.334(a)(2)(ii): There was a defect or evidence of damage that could have exposes an employee to injury and the defective or damaged item was not removed from service. Warehouse garage bay work bench area; on or about 21 May 2019 and times prior thereto; a Central Machinery 8-inch Bench Grinder, stock number S34324 had a damaged power cord. This condition exposed employees to electrical shock and electrical burn hazards.
Recent events (1)
- — Z (S) $0
1910.22 D01
- Issued
- May 31, 2019
- Abate by
- Jul 3, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.22(d)(1): In every building or other structure, or part thereof, used for mercantile, business, industrial, or storage purposes, the loads approved by the building official were not marked on plates of approved design which were not supplied and securely affixed by the owner of the building, or his duly authorized agent, in a conspicuous place in each space to which they relate. Warehouse garage bay mezzanine above Resources office; on or about 21 May 2019 and times prior thereto; the mezzanine storage area did not have the maximum safe load limit conspicuously posted. This condition exposed employees to a struck by hazard.
Recent events (1)
- — Z (O) $0
1910.37 A01
- Issued
- May 31, 2019
- Abate by
- Jul 3, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(a)(1): Exit routes shall not have flammable, explosive, combustible gases or flammable furnishings stored in the exit route. Warehouse bottom of stairway leading to the Planning area; on or about 21 May 2019 and times prior thereto; the employer did not ensure that each designated exit route was free of flammable, explosive, or combustible gases. A five-gallon propane tank was stored at the bottom of the stairway along the designated exit route. This condition exposed employees to fire, explosion and tripping hazards.
Recent events (1)
- — Z (O) $0
1910.37 A04
- Issued
- May 31, 2019
- Abate by
- Jul 3, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(a)(4): Safeguard(s) designed to protect employees during an emergency (e.g., sprinkler systems, alarm systems, fire doors, exit lighting), were not in proper working order at all times. Warehouse building; on or about 21 May 2019 and times prior thereto; the employer did not ensure that emergency exit lighting was in proper working order. Five instances were noted: a. Garage bay adjacent to latrine. b. Warehouse wood shop exterior door. c. Warehouse bottom of stairway leading to the Planning area. d. Warehouse Planning area upstairs exterior exit. e. Warehouse Planning area upstairs top of stairwell. This condition exposed employees to delays in exiting the building, smoke inhalation, fire, and tripping hazards.
Recent events (1)
- — Z (O) $0
1910.37 B02
- Issued
- May 31, 2019
- Abate by
- Jul 3, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(b)(2): Each exit was not clearly visible and marked by a sign reading "Exit". Warehouse storage bay; on or about 21 May 2019 and times prior thereto; the employer did not ensure that exits signs were posted. Two instances were noted: a. Warehouse freight storage area doorway to Planning area; was not marked with an exit sign. b. Warehouse freight storage bay doorway to exterior exit; was not marked with an exit sign. This condition exposed employees to delays in exiting the building, smoke inhalation, fire, and tripping hazards.
Recent events (1)
- — Z (O) $0
1910.37 B05
- Issued
- May 31, 2019
- Abate by
- Jul 3, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(b)(5): Each doorway or passage along an exit access that could be mistaken for an exit was not marked "Not an Exit" or similar designation, or be identified by a sign indicating its actual use (e.g. closet). Warehouse building; on or about 21 May 2019 and times prior thereto; the employer did not ensure that each doorway along a designated exit path was marked as "not an exit" or other signage indicating its actual use. Three instances were noted: a. Warehouse freight bay doorway leading to Survey Engineers room not marked as "not an exit" or other identifying signage. b. Warehouse bottom of the stairway leading to Planning area; on the left-hand side of the doorway leading to the freight bay, was not marked as "not an exit" or other identifying signage. c. Warehouse bottom of the stairway leading to Planning area; on the right-hand side doorway leading to the supply storage cage, was not marked as "not an exit" or other identifying signage. This condition exposed employees to delays in exiting the building causing smoke inhalation and fire hazards.
Recent events (1)
- — Z (O) $0
1910.151 C
- Issued
- May 31, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.151(c): Where employees were exposed to injurious corrosive materials, suitable facilities for quick drenching or flushing of the eyes and body were not provided within the work area for immediate emergency use. Warehouse garage bay across from welding area; on or about 21 May 2019 and times prior thereto; the plumbed eye wash station was blocked. Miscellaneous items were stored in front of the eye wash station impeding immediate access. This condition exposed employees to an eye trauma hazard.
Recent events (1)
- — Z (O) $0
1910.157 E02
- Issued
- May 31, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(e)(2): Portable fire extinguishers were not visually inspected at least monthly. Throughout the worksite; the employer did not ensure that portable fire extinguishers were visually inspected at least monthly. Nine instances were noted: a. Warehouse garage bay adjacent to compressor cage area; an Amerex Model B456, serial number B-76387032 was not visually inspected at least monthly. Last indicated monthly inspection was January 2019. b. Warehouse garage bay adjacent to maintenance office; an Amerex Model B402, serial number C-89893843 had no indicated monthly inspection recorded. Last annual inspection was November 2018. c. Warehouse garage bay adjacent to Resources office; an Amerex Model 423, serial number XD-699415 as not visually inspected at least monthly. Last indicated monthly inspection was January 2019. d. Warehouse garage bay adjacent to the stairwell and latrine area; an Amerex Model 423, serial number K-291229, was not visually inspected at least monthly. Last indicated monthly inspection was January 2019. e. Warehouse fire office; an Amerex, Model B402, serial number G-847061 had no indicated monthly inspection recorded. Last annual inspection was November 2018. f. Warehouse Planning area adjacent to the storage room; an Amerex Model 402, serial number YS-304768 as not visually inspected at least monthly. Last indicated monthly inspection was January 2019. g. Recreation flammable storage conex; an Amerex Model and serial number unknown, had no indicated monthly inspection recorded. Last annual inspection was November 2018. h. Administrative building computer room; an Amerex Model B441, serial number SG-842453 as not visually inspected at least monthly. Last indicated monthly inspection was January 2019. i. Administrative building computer room; an Amerex Model Halon 1211, serial number B-220631 was not visually inspected at least monthly. Last indicated monthly inspection was January 2019. This condition exposed employees to fire and smoke inhalation hazards.
Recent events (1)
- — Z (O) $0
1910.178 Q07
- Issued
- May 31, 2019
- Abate by
- Jul 3, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.178(q)(7): Industrial trucks were not examined before being placed in service. Warehouse garage bay; on or about 21 May 2019 and times prior thereto; the employer did not ensure that the Toyota Forklift Truck, model 42-4FG25, serial number 21175 was inspected prior to use. Powered industrial truck examinations/ inspections were not performed to detect for possible defects or issues involving, but not limited to, the following: damage, tires/wheels, steering, forward and reverse travel controls, safety devices such as the emergency button for reversing direction, hydraulic systems (leaks, bad lines), brakes, inadequate stopping distance, horn, and battery connectors. This condition exposed employees to unsafe administrative practices.
Recent events (1)
- — Z (O) $0
1910.213 S06
- Issued
- May 31, 2019
- Abate by
- Jul 3, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.213(s)(6): Cleanliness around working machinery was not maintained to prevent fire hazards and ensure the effective functioning of guards. Warehouse woodshop area; on or about 21 May 2019 and times prior thereto; the employer did not ensure that the area around woodworking machinery was kept clean to minimize fire and struck by hazards. No dust control was utilized. Miscellaneous items such as screws and cut-off ends were left in the immediate work area. This condition exposed employees to struck by and fire hazards.
Recent events (1)
- — Z (O) $0
1910.244 A02 VI A
- Issued
- May 31, 2019
- Abate by
- Jul 3, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.244(a)(2)(vi)(a): Each jack used constantly or intermittently at a single locality was not thoroughly inspected at least once every six months. Warehouse garage bay; on or about 21 May 2019 and times prior thereto; the employer did not ensure that a Meyer hydraulic TJC multi-purpose floor crane and jack combination, serial number 10050401107 was inspected at least every six months. No inspection log was maintained. This condition exposed employees to caught under hazard.
Recent events (1)
- — Z (O) $0
1910.305 B02 I
- Issued
- May 31, 2019
- Abate by
- Jul 3, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(2)(i): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy. Warehouse electrical room; on or about 21 May 2019 and times prior thereto; an energized electrical outlet did not have the face plate installed. This condition exposed employees to electrical shock and electrical burn hazards.
Recent events (1)
- — Z (O) $0
1910.1030 G01 I A
- Issued
- May 31, 2019
- Abate by
- Jul 3, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.1030(g)(1)(i)(A): Warning labels were not affixed to containers of regulated waste, refrigerators, or freezers containing blood or other potentially infectious material. Warehouse freight bay; on or about 21 May 2019 and times prior thereto; the GE Refrigerator model and serial number unknown, used to store biological specimens did not have warning labels affixed. This condition exposed employees to biological hazards.
Recent events (1)
- — Z (O) $0
1910.1200 F06 I
- Issued
- May 31, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.1200(f)(6)(i): Except as provided in 29 CFR 1910.1200(f)(7) and 29 CFR 1910.1200(f)(8), the employer did not ensure that each container of hazardous chemicals in the workplace was labeled, tagged or marked with the information required by 29 CFR 1910.1200(f)(1)(i) through 29 CFR 1910.1200(f)(1)(v) Warehouse garage bay workbench; on or about 21 May 2019 and times prior thereto an unmarked plastic bottle; containing an unknown chemical substance was not marked identifying the product and the hazard warnings associated with it. This condition exposed employees to chemical burns, poisoning, and skin dermatitis.
Recent events (1)
- — Z (O) $0
1910.1200 H03 IV
- Issued
- May 31, 2019
- Abate by
- Jul 3, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.1200(h)(3)(iv): The details of the hazard communication program developed by the employer, did not include an explanation of the labels received on shipped containers and the workplace labeling system used by their employer; the safety data sheet, including the order of information and how employee could obtain and use the appropriate hazard information. Administrative Building; on or about 21 May 2019 and times prior thereto; employees were not trained on the new Hazard Communications Standard (HCS 2012) provisions implemented on 1 December 2013. This training includes revised labeling elements and the new format for Safety Data Sheets. This condition exposed employees to inadequate training and chemical hazards.
Recent events (1)
- — Z (O) $0
More inspections at U.S. Forest Service, Thorne BAY Ranger District
View U.S. Forest Service, Thorne BAY Ranger District's full OSHA safety record →
More inspections in this industry (NAICS 924120)
More inspections in AK
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 344032347.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.