PAGO PAGO, AS —
OSHA Inspection: O & O INC.
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of O & O INC. in MAIN ROAD, NUULI, PAGO PAGO, AS 96799 (NAICS 424410). OSHA activity number 344034129.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- O & O INC.
- Site address
- MAIN ROAD, NUULI
- City
- PAGO PAGO
- State
- AS
- ZIP
- 96799
- Mailing
- PO BOX 3897, PAGO PAGO, AS 96799
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 424410
- Employees
- 35
- Ownership type
- A
Citations
3 citations on file for this inspection.
1910.305 B02 I
- Issued
- Jul 19, 2019
- Abate by
- Jul 29, 2019
- Penalty
- Initial $3,978 · Current $2,785 Reduced
General-duty citation text
29 CFR 1910.305(b)(2)(i): All pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose; and each outlet box in completed installations did not have a cover, faceplate, or fixture canopy: a. Ladies section south wall below the panel: An outlet without a faceplate exposed employees to electrical hazards. b. Ladies section east wall below the AC: An outlet without a faceplate exposed employees to electrical hazards. c. Warehouse display room across from the entrance: An outlet without a faceplate exposed employees to electrical hazards.
Recent events (2)
- — I (S) $2784.6
- — Z (S) $3978
1910.305 D02
- Issued
- Jul 19, 2019
- Abate by
- Jul 29, 2019
- Penalty
- Initial $6,631 · Current $4,642 Reduced
General-duty citation text
29 CFR 1910.305(d)(2): Panel boards were not dead front. a. Ladies section south wall: The electrical circuit breaker panel cover was missing, exposing employees to fire and electrical hazards b. Warehouse entrance left wall: The electrical circuit breaker panel cover was missing, exposing employees to fire and electrical hazards
Recent events (2)
- — I (S) $4641.7
- — Z (S) $6631
1910.303 G01
- Issued
- Jul 19, 2019
- Abate by
- Jul 26, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment: Left side warehouse entrance: Boxes of merchandises were blocking access to the electrical panel in the event of emergency exposing employees to electrical and fire hazards.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at O & O INC.
View O & O INC.'s full OSHA safety record →
More inspections in this industry (NAICS 424410)
More inspections in AS
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 344034129.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.