Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: NORTHSHORE BROADCASTING COMPANY, INC.

Unprogrammed Related inspection · Safety discipline

On , OSHA opened an unprogrammed Related safety inspection of NORTHSHORE BROADCASTING COMPANY, INC. in SOUTH 2ND AND OLD BROOK RD, BROOKHAVEN, MS 39601 (NAICS 515112). OSHA activity number 344049473.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Northshore Broadcasting Company, INC. — free Get an email when a new federal OSHA severe-injury report for Northshore Broadcasting Company, INC. is published. One employer, no account, unsubscribe in one click.
Site address
SOUTH 2ND AND OLD BROOK RD
City
BROOKHAVEN
State
MS
ZIP
39601
Mailing
200 EAST THOMAS STREET, HAMMOND, LA 70401
Inspection type
Unprogrammed Related (G)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
515112
Employees
2
Ownership type
A

5 citations on file for this inspection.

1910.303 F02

Serious Gravity 5 1 instance 2 exposed
Issued
Nov 14, 2019
Abate by
Jan 9, 2020
Penalty
Initial $5,304 · Current $2,122 Reduced
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident:    (a) Transmission Room at South 2nd and Old Brook Rd, Brookhaven MS - On or about May 17, 2019 circuit breakers next to the entrance of the transmission room were not labeled, exposing employees to electrical hazards.
Recent events (2)
  • — I (S) $2121.6
  • — Z (S) $5304

1910.303 G02 I

Serious Gravity 5 1 instance 2 exposed
Issued
Nov 14, 2019
Abate by
Jan 9, 2020
Penalty
Initial $5,304 · Current $2,122 Reduced
29 CFR 1910.303(g)(2)(i): Live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by approved cabinets or other forms of approved enclosures, or other means listed under this provision:    (a) Transmission Room - On or about May 17, the circuit breaker box was missing the faceplate, exposing employees to electrical hazards.
Recent events (2)
  • — I (S) $2121.6
  • — Z (S) $5304

1910.305 B01 III

Serious Gravity 5 1 instance 2 exposed
Issued
Nov 14, 2019
Abate by
Jan 9, 2020
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(1)(iii): Cable was not secured to the cabinet, cutout box, or meter socket enclosure:    (a) Transmission Room - On or about May 17, 2019 live electrical wires were not secured within the breaker box, exposing employees to electrical hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.101 B

Other-than-serious 1 instance 2 exposed
Issued
Nov 14, 2019
Abate by
Jan 9, 2020
Penalty
Initial $0 · Current $0
29 CFR 1910.101(b): The in-plant handling, storage, and utilization of all compressed gases were not in accordance with Compressed Gas Association Pamphlet P-1-1965, which is incorporated by reference as specified in Sec. 1910.6.    (a) Transmission Room - On or about May 17, 2019, the nitrogen cylinder stored by the entrance to the transmission room did not have the label as required by Section 3.1.8 of the Compressed Gas Pamphlet, exposing employees to unknown gasses.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.305 G01 IV A

Other-than-serious 1 instance 2 exposed
Issued
Nov 14, 2019
Abate by
Jan 9, 2020
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(A): Unless specifically permitted otherwise in paragraph (g)(1)(ii) of this section, flexible cords and cables may not be used as a substitute for permanent building wiring.    (a) Transmission building -  On or about May 17, 2019 extension cords were utilized as permanent wiring exposing employees to electrical hazards.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View Northshore Broadcasting Company, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 344049473.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.