Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: TRUONG ENTERPRISES, INC

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of TRUONG ENTERPRISES, INC in 8080 TRANSIT ROAD, WILLIAMSVILLE, NY 14221 (NAICS 236220). OSHA activity number 344076419.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Truong Enterprises, INC — free Get an email when a new federal OSHA severe-injury report for Truong Enterprises, INC is published. One employer, no account, unsubscribe in one click.
Site address
8080 TRANSIT ROAD
City
WILLIAMSVILLE
State
NY
ZIP
14221
Mailing
8080 TRANSIT ROAD, WILLIAMSVILLE, NY 14221
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
236220
Employees
1
Ownership type
A

3 citations on file for this inspection.

1926.403 I02 I

Serious Gravity 1 1 instance 1 exposed
Issued
Aug 14, 2019
Penalty
Initial $1,642 · Current $1,149 Reduced
29 CFR 1926.403(i)(2)(i): Live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by cabinets or other forms of enclosures, nor by any of the means listed in subparagraphs (A) through (D) of this paragraph:   a) On or about 6/11/19, at the washroom area of the site, Williamsville, NY. Hot and neutral wires were pulled out of a wall junction box and connected to the female end of a flexible cord to power temporary lighting. Energized conductors of 120 volts were not guarded against accidental contact.   NO ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
  • — I (S) $1149
  • — Z (S) $1642

1926.403 I01 II

Other-than-serious 1 instance 1 exposed
Issued
Aug 14, 2019
Penalty
Initial $0 · Current $0
29 CFR 1926.403(i)(1)(ii): Working space about electric equipment operating at 600 volts, nominal, or less was used for storage:   a) On or about 6/11/19, at the electric panel area of the site, Williamsville, NY. Working space for electric panels was used for storage of kitchen fryers.   NO ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1926.405 A02 II E

Other-than-serious 1 instance 1 exposed
Issued
Aug 14, 2019
Penalty
Initial $0 · Current $0
29 CFR 1926.405(a)(2)(ii)(E): Lamps used in temporary wiring for general illumination were not protected from accidental contact or breakage:   a) On or about 6/11/19 at the kitchen area of the site, Williamsville, NY. Temporary lights was hanging 3 to 4 feet from the ground and did not have protection cage for accidental contact or breakage.   NO ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 344076419.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.