CARROLLTON, TX —
OSHA Inspection: SWISS AMERICAN CDMO LLC
Complaint inspection · Health discipline
At a glance
On , OSHA opened a complaint health inspection of SWISS AMERICAN CDMO LLC in 2055 LUNA ROAD, CARROLLTON, TX 75006 (NAICS 325412). OSHA activity number 344100730.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- SWISS AMERICAN CDMO LLC
- Site address
- 2055 LUNA ROAD
- City
- CARROLLTON
- State
- TX
- ZIP
- 75006
- Mailing
- 2055 LUNA ROAD, CARROLLTON, TX 75006
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 325412
- Employees
- 300
- Ownership type
- A
Citations
5 citations on file for this inspection.
1910.106 E02 II B 2
- Issued
- Oct 31, 2019
- Abate by
- Dec 19, 2019
- Penalty
- Initial $13,260 · Current $13,260
General-duty citation text
29 CFR 1910.106(e)(2)(ii)(b)(2): More than 120 gallons of Category 2, 3, or 4 flammable or combustible liquids in containers were located outside of inside storage room(s) or storage cabinet(s): On or about June 21, 2019, in the warehouse next to the weighing area, where more than 120 gallons of isopropyl alcohol and ethyl alcohol were stored, exposing employees to fire hazards.
Recent events (1)
- — Z (S) $13260
1910.106 E06 II
- Issued
- Oct 31, 2019
- Abate by
- Dec 19, 2019
- Penalty
- Initial $13,260 · Current $13,260
General-duty citation text
29 CFR 1910.106(e)(6)(ii): Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100 °F (37.8 °C), were dispensed into containers without the nozzle and container being electrically interconnected: This violation was discovered on June 21, 2019, in the weighing room, where employees dispensed category 2 flammable liquids, 99% proof isopropyl alcohol and 200 proof ethyl alcohol, from 55 gallon drums into smaller containers and the nozzle and container were not electrically interconnected.
Recent events (1)
- — Z (S) $13260
1910.134 E01
- Issued
- Oct 31, 2019
- Abate by
- Dec 19, 2019
- Penalty
- Initial $13,260 · Current $13,260
General-duty citation text
29 CFR 1910.134(e)(1): The employer did not provide a medical evaluation to determine the employee's ability to use a respirator, before the employee was fit tested or required to use the respirator in the workplace: This violation was discovered on June 21, 2019, in the production area, where the employer allowed employees to use Honeywell full face elastomeric respirators without providing those employees a medical evaluation to determine the employee's fitness to wear a respirator.
Recent events (1)
- — Z (S) $13260
1910.134 F01
- Issued
- Oct 31, 2019
- Abate by
- Dec 19, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.134(f)(1): The employer did not ensure that employee(s) required to use a tight-fitting facepiece respirator passed the appropriate qualitative fit test (QLFT) or quantitative fit test (QNFT): This violation was discovered on June 21, 2019, in the production area, where the employer allowed employees to use Honeywell full face elastomeric respirators without requiring those employees to pass a qualitative fit test or quantitative fit test.
Recent events (1)
- — Z (S) $0
1910.1200 E01
- Issued
- Oct 31, 2019
- Abate by
- Dec 19, 2019
- Penalty
- Initial $13,260 · Current $13,260
General-duty citation text
29 CFR 1910.1200(e)(1): The employer did not develop, implement, and/or maintain at the workplace a written hazard communication program which describes how the criteria specified in 29 CFR 1910.1200(f), (g), and (h) will be met: This violation was discovered on June 21, 2019, in the production area, where employees handled hazardous chemicals but the employer did not have a written hazard communication program in place.
Recent events (1)
- — Z (S) $13260
More inspections at Swiss American Cdmo LLC
View Swiss American Cdmo LLC's full OSHA safety record →
More inspections in this industry (NAICS 325412)
More inspections in TX
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 344100730.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.