Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: PRAXAIR DISTRIBUTION INC.

Planned inspection · Health discipline

On , OSHA opened a planned health inspection of PRAXAIR DISTRIBUTION INC. in 321 ROANOKE AVE, NEWARK, NJ 07105 (NAICS 424690). OSHA activity number 344113360.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Praxair Distribution INC. — free Get an email when a new federal OSHA severe-injury report for Praxair Distribution INC. is published. One employer, no account, unsubscribe in one click.
Site address
321 ROANOKE AVE
City
NEWARK
State
NJ
ZIP
07105
Mailing
321 ROANOKE AVE, NEWARK, NJ 07105
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
424690
Employees
11
Ownership type
A

4 citations on file for this inspection.

1910.28 B03 II

Other-than-serious 2 instances 8 exposed
Issued
Dec 19, 2019
Abate by
Jan 14, 2020
Penalty
Initial $7,577 · Current $7,577
29 CFR 1910.28(b)(3)(ii):  Each employee was not  protected from tripping into or stepping into or through any hole that is less than 4 feet (1.2 m) above a lower level by covers or guardrail systems:    Workplace, 321 Roanoke Avenue, Newark, NJ    In an acetylene repackaging facility, employees operate and inspect "Rexarc" compressors that step up pressure of acetylene to dispense into acetylene cylinders with fill material and acetone that adsorb the acetylene under pressure:    a)  In the "Rexarc" compressor room, where  employees operate and inspect the compressors, there is a floor hole approximately 8 inches in length and width and depth, that employees can step into while working and walking around the compressors.     b)  In the "Rexarc" compressor room, where  employees operate and inspect the compressors, there is a floor hole approximately 14 inches in length, 6 inches in width and 12 inches in depth, that employees can step into while working and walking around the compressors.     Violation occurred on or about 11/06/2019
Recent events (2)
  • — I (O) $7577
  • — Z (S) $7577

1910.101 B

Other-than-serious 1 instance 4 exposed
Issued
Dec 19, 2019
Penalty
Initial $9,472 · Current $9,472

Hazardous substances 0070

29 CFR 1910.101(b): Cylinders were not stored or handled in accordance with appropriate standards of the Compressed Gas Association Pamphlet P-1-1965,  Sections 3.3.1 and 3.3.8, which is incorporated by reference as specified in CFR 1910.6:      a) Workplace, 321 Roanoke Avenue, Newark, NJ      In the Acetylene Filling Room, eight (8) full acetylene 100 ft3 cylinders were painted and left to dry without protective valve caps near an emergency exit and loading dock bay door used by employees.  The employer did not ensure the cylinders were chained or otherwise secured from being knocked over, creating a potential projectile, fire, and/or explosion hazard.      Violation observed 11-6-19
Recent events (2)
  • — I (O) $9472
  • — Z (S) $9472

1910.119 F04

Other-than-serious 1 instance 1 exposed
Issued
Dec 19, 2019
Abate by
Feb 14, 2020
Penalty
Initial $9,472 · Current $9,472

Hazardous substances 0070

29 CFR 1910.119(f)(4): The employer did not implement safe work practices to provide for the control of hazards during operations such as lockout/tagout; confined space entry; opening process equipment or piping; and control over entrance into a facility by maintenance, contractor, laboratory, or other support personnel:    Workplace, 321 Roanoke Avenue, Newark, NJ    a) On or about 09/10/19 the employer failed to maintain specific written steps for lockout/tagout with regard to maintenance on the stage 3 blowdown valve on Compressor 5.
Recent events (2)
  • — I (O) $9472
  • — Z (S) $9472

1910.147 C04 II B

Deleted Serious Gravity 5 1 instance 1 exposed
Issued
Dec 19, 2019
Abate by
Jan 14, 2020
Penalty
Initial $0 · Current $0

Hazardous substances 0070

29 CFR 1910.147(c)(4)(ii)(B): The energy control procedures did not clearly and specifically outline the steps for shutting down, isolating, blocking and securing machines or equipment to control hazardous energy:  Compressor Room, 321 Roanoke Avenue, Newark, NJ  a)  In an acetylene repackaging facility, employees perform maintenance on process equipment, such as Compressors, including but not limited to replacing a leaking blowdown valve D53J on Compressor 5 Stage 3.  The employer did not implement safe work practices in that  the employer did not maintain written lock out tag out procedures with specific steps to follow to isolate and control chemical, mechanical and electrical residual energy prior to conducting maintenance activities.    Violation occurred on or about 09/10/2019
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

View Praxair Distribution INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 344113360.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.