JONESVILLE, LA —
OSHA Inspection: CONCORDIA ELECTRIC COOPERATIVE, INC.
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of CONCORDIA ELECTRIC COOPERATIVE, INC. in HWY 126, JONESVILLE, LA 71343 (NAICS 221122). OSHA activity number 344124755.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- CONCORDIA ELECTRIC COOPERATIVE, INC.
- Site address
- HWY 126
- City
- JONESVILLE
- State
- LA
- ZIP
- 71343
- Mailing
- PO BOX 98, JONESVILLE, LA 71343
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 221122
- Employees
- 64
- Ownership type
- A
Citations
10 citations on file for this inspection.
1910.37 B06
- Issued
- Dec 23, 2019
- Abate by
- Dec 30, 2019
- Penalty
- Initial $4,048 · Current $1,000 Reduced
General-duty citation text
29 CFR 1910.37(b)(6): Each exit sign was not illuminated to a surface value of at least five foot-candles (54 lux) by a reliable light source and be distinctive in color: On or about June 25, 2019, in the middle hallway at the main office, exit signs were not in working order and not illuminated throughout the building: a) Exit sign above the entrance to the hallway of the office was not illuminated. b) Exit sign above the entrance to the hallway was damaged and not illuminated.
Recent events (2)
- — I (O) $1000
- — Z (S) $4048
1910.269 A04
- Issued
- Dec 23, 2019
- Abate by
- Jan 3, 2020
- Penalty
- Initial $6,747 · Current $3,978 Reduced
General-duty citation text
29 CFR 1910.269(a)(4): Existing characteristics and conditions of electric lines and equipment that were related to the safety of the work to be performed was not determined before work on or near the lines or equipment was started. Such characteristics and conditions include, but not limited to 1910.269(a)(4)(i) through 1910.269(a)(4)(viii): On or about June 25, 2019, north side of an electrical pole, employees were running a new electrical line from an ungrounded utility service truck to replace a damaged 14.4KVA electrical line to restore power to local residence.
Recent events (2)
- — I (S) $3978
- — Z (S) $6747
1910.269 C01 I
- Issued
- Dec 23, 2019
- Abate by
- Jan 9, 2020
- Penalty
- Initial $9,446 · Current $5,569 Reduced
General-duty citation text
29 CFR 1910.269(c)(1)(i): A more extensive job briefing was not conducted where an employee could not be expected to recognize and avoid the hazards involved in the job: On or about June 25, 2019, on the North side of an electrical power pole, employees were servicing a down 14.4KVA electrical power line without a job briefing or job assessment of the hazards associated with working on live electrical lines.
Recent events (2)
- — I (S) $5569.2
- — Z (S) $9446
1910.269 C01 II
- Issued
- Dec 23, 2019
- Abate by
- Jan 9, 2020
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.269(c)(1)(ii): The employer did not ensure that the employee in charge conducted a job briefing that met paragraphs (c)(2) though (c)(4) of this section with the employees involved before they start each job: On or about June 25, 2019, on the North side of an electrical power pole, the employer did not ensure that employees were servicing a down 14.4KVA power line without a job briefing or job assessment of the hazards associated with working on live electrical lines.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.269 D02 I
- Issued
- Dec 23, 2019
- Abate by
- Jan 9, 2020
- Penalty
- Initial $9,446 · Current $5,569 Reduced
General-duty citation text
29 CFR 1910.269(d)(2)(i): The employer shall establish a program consisting of energy control procedures, employee training, and periodic inspections to ensure that, before any employee performs any servicing or maintenance on a machine or equipment where the unexpected energizing, start up, or release of stored energy could occur and cause injury, the machine or equipment is isolated from the energy source and rendered inoperative: On or about June 25, 2019, on the North side of an electrical power pole, employees were servicing a down 14.4KVA electrical power line without an energy control program, associated training, or periodic inspections with isolating 14.4KVA electrical lines.
Recent events (2)
- — I (S) $5569.2
- — Z (S) $9446
1910.269 D02 V
- Issued
- Dec 23, 2019
- Abate by
- Jan 2, 2020
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.269(d)(2)(v): The employer did not conduct a periodic inspection of the energy control procedure at least annually to ensure that the procedure and the provisions of paragraph (d) of this section were being followed: On or about June 25, 2019, on the North side of an electrical power pole, employee were servicing a down 14.4KVA electrical power line without annual evaluation of the energy control procedures.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.269 G02 I
- Issued
- Dec 23, 2019
- Abate by
- Jan 2, 2020
- Penalty
- Initial $9,446 · Current $5,569 Reduced
General-duty citation text
29 CFR 1910.269(g)(2)(i): (i) Personal fall arrest systems shall meet the requirements of 29 CFR part 1910, subpart I: Employees utilized aerial lift service trucks without the use of fall protection.
Recent events (2)
- — I (S) $5569.2
- — Z (S) $9446
1910.335 A01 I
- Issued
- Dec 23, 2019
- Abate by
- Dec 30, 2019
- Penalty
- Initial $9,446 · Current $0 Reduced
General-duty citation text
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not provided with electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected and for the work being performed: On or about June 25, 2019, North side of an electrical pole, employees were installing a new electrical line to replace a damaged 14.4KVA electrical line without flame resistant (FR) clothing to restore power to local clients.
Recent events (2)
- — I (S) $0
- — Z (S) $9446
1910.1200 E01
- Issued
- Dec 23, 2019
- Abate by
- Dec 30, 2019
- Penalty
- Initial $4,048 · Current $500 Reduced
General-duty citation text
29 CFR 1910.1200(e)(1): The employer did not develop, implement, and maintain at each workplace, a written hazard communication program which described how the criteria specified in 29 CFR 1910.1200 paragraphs (f), (g), and (h) for labels and other forms of warning, safety data sheets, and employee information and training would be met. On or about June 25, 2019, North side of an electrical pole, the employer did not develop and implement a hazard communication program for employee(s) utilizing a weed killer containing hazardous chemicals including, but not limited to diethylene, thiadiazol, and dichlorophenol in the field when servicing electrical poles.
Recent events (2)
- — I (O) $500
- — Z (S) $4048
1910.1200 H01
- Issued
- Dec 23, 2019
- Abate by
- Dec 30, 2019
- Penalty
- Initial $0 · Current $500
General-duty citation text
29 CFR 1910.1200(h)(1): Employees were not provided effective information and training on hazardous chemicals in their work area at the time of their initial assignment and whenever a new hazard that the employees had not been previously trained about was introduced into their work area: On or about June 25, 2019, North side of an electrical pole, the employees were not provided training on hazardous chemicals at their job site prior to clearing weeds with weed killer containing, but not limited to diethylene, thiadiazol, and dichlorophenol in the field when servicing electrical poles.
Recent events (2)
- — I (O) $500
- — Z (S) $0
More inspections at Concordia Electric Cooperative, INC.