OSHA Inspection: GAURVI HOSPITALITY LLC

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of GAURVI HOSPITALITY LLC in 2260 WHITNEY AVENUE, HAMDEN, CT 06518 (NAICS 721110). OSHA activity number 344128202.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Gaurvi Hospitality LLC — free Get an email when a new federal OSHA severe-injury report for Gaurvi Hospitality LLC is published. One employer, no account, unsubscribe in one click.
Site address
2260 WHITNEY AVENUE
City
HAMDEN
State
CT
ZIP
06518
Mailing
2260 WHITNEY AVENUE, HAMDEN, CT 06518
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
721110
Employees
40
Ownership type
A

11 citations on file for this inspection.

1910.22 A01

Serious Gravity 5 2 instances 20 exposed
Issued
Sep 26, 2019
Abate by
Oct 2, 2019
Penalty
Initial $6,630 · Current $4,620 Reduced
29 CFR 1910.22(a)(1): All places of employment, passageways, storerooms, service rooms, and walking-working surfaces were not kept in a clean, orderly, and sanitary condition.    Establishment:  The Walking-Working surfaces in the following locations were not maintained in a clean safe condition:    A. Pool Pump Room: The cover to the sump well was not in place exposing the employees to tripping hazards.       B.Main Electrical Room: The channel iron that was on the floor and extended to the interior of the main electrical switch for the hotel was creating tripping and electrical hazards.
Recent events (2)
  • — I (S) $4620
  • — Z (S) $6630

1910.37 A03

Serious Gravity 5 1 instance 20 exposed
Issued
Sep 26, 2019
Abate by
Oct 2, 2019
Penalty
Initial $5,304 · Current $3,730 Reduced
29 CFR 1910.37(a)(3): Exit route(s) were not kept free and unobstructed:    Establishment:  The fire exit in the rear lower stairwell was blocked.
Recent events (2)
  • — I (S) $3730
  • — Z (S) $5304

1910.157 C01

Serious Gravity 1 3 instances 20 exposed
Issued
Sep 26, 2019
Abate by
Oct 8, 2019
Penalty
Initial $3,978 · Current $2,700 Reduced
29 CFR 1910.157(c)(1): Portable fire extinguishers were not mounted, located and identified so that they were readily accessible without subjecting the employees to injuries:    Establishment: The portable fire extinguishers were not properly mounted and identified for use.
Recent events (2)
  • — I (S) $2700
  • — Z (S) $3978

1910.157 E03

Serious Gravity 1 3 instances 30 exposed
Issued
Sep 26, 2019
Abate by
Oct 8, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.157(e)(3): Portable fire extinguishers were not subjected to an annual maintenance check:  Establishment: The employer did not ensure that portable fire extinguishers were subjected to an annually maintenance service.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.303 B07 I

Serious Gravity 5 3 instances 20 exposed
Issued
Sep 26, 2019
Abate by
Oct 8, 2019
Penalty
Initial $5,304 · Current $3,730 Reduced
29 CFR 1910.303(b)(7)(i): Unused openings in boxes, raceways, auxiliary gutters, cabinets, equipment cases, or housings shall be effectively closed to afford protection substantially equivalent to the wall of the equipment.    Main Electrical Room: The high voltage circuit breaker panel had few unused openings that were not effectively closed.
Recent events (2)
  • — I (S) $3730
  • — Z (S) $5304

1910.303 B07 IV

Serious Gravity 5 1 instance 20 exposed
Issued
Sep 26, 2019
Abate by
Oct 8, 2019
Penalty
Initial $5,304 · Current $3,730 Reduced
29 CFR 1910.303(b)(7)(iv): There were damaged parts that could adversely affect safe operation or mechanical strength of the equipment, such as parts that were broken, bent, cut, or deteriorated by corrosion, chemical action, or overheating.    Main Electrical Room: The bottom of the main breaker cabinet and adjoining high voltage breaker panels were rusted and not maintained the same mechanical strength.
Recent events (2)
  • — I (S) $3730
  • — Z (S) $5304

1910.305 E01

Serious Gravity 5 1 instance 20 exposed
Issued
Sep 26, 2019
Abate by
Oct 8, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.305(e)(1): Cabinets, cutout boxes, fittings, boxes, and panelboard enclosures. Cabinets, cutout boxes, fittings, boxes, and panelboard enclosures in damp or wet locations were not installed so as to prevent moisture or water from entering and accumulating within the enclosures and were not mounted so there is at least 6.35-mm (0.25-in.) airspace between the enclosure and the wall or other supporting surface. However, nonmetallic enclosures may be installed without the airspace on a concrete, masonry, tile, or similar surface. The enclosures shall be weatherproof in wet locations.  Main Electrical Room: The main breaker panel and the high voltage circuit panel were installed in wet location and were not installed to protect the equipment from damage.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.303 G02 I

Serious Gravity 5 1 instance 20 exposed
Issued
Sep 26, 2019
Abate by
Oct 8, 2019
Penalty
Initial $5,304 · Current $3,730 Reduced
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by this standard, live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the following means:    Pool Room: The live parts of the internal wiring of the pool water heater was not covered and/or protected.
Recent events (2)
  • — I (S) $3730
  • — Z (S) $5304

1910.305 B02 I

Serious Gravity 5 1 instance 20 exposed
Issued
Sep 26, 2019
Abate by
Oct 8, 2019
Penalty
Initial $5,304 · Current $3,730 Reduced
29 CFR 1910.305(b)(2)(i): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy.    Lower Hallway: The outlets installed on the fixture wall were missing faceplates or covers, exposing internal wiring.
Recent events (2)
  • — I (S) $3730
  • — Z (S) $5304

1910.305 G01 IV A

Serious Gravity 5 1 instance 20 exposed
Issued
Sep 26, 2019
Abate by
Oct 8, 2019
Penalty
Initial $5,304 · Current $3,730 Reduced
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:    Maintenance Office:  A flexible cord extended one room to another to provide power to a shelf area where numerous tools and batteries were stored.
Recent events (2)
  • — I (S) $3730
  • — Z (S) $5304

1904.33 A

Other-than-serious 1 instance 40 exposed
Issued
Sep 26, 2019
Abate by
Oct 8, 2019
Penalty
Initial $1,327 · Current $900 Reduced
29 CFR 1904.33(a): The employer did not save a log of all Work-Related Injuries and Illnesses (OSHA Form 300), the Privacy Case List (if one exists), the Summary of Work-Related Injuries and Illnesses (OSHA Form 300-A), and the Injury and Illness Incident Report (OSHA Form 301) for five (5) years following the end of the calendar year that these records cover:        ESTABLISHMENT: The employer had not maintained the log of all Work-Related Injuries and Illnesses (OSHA Form 300) and the Summary of Work-Related Injuries and Illnesses (OSHA Form 300-A) for the years of 2014 through 2018.
Recent events (2)
  • — I (O) $900
  • — Z (O) $1327

View Gaurvi Hospitality LLC's full OSHA safety record →