DENISON, TX —
OSHA Inspection: MOFFITT WEST
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of MOFFITT WEST in 3100 JUANITA DR., DENISON, TX 75020 (NAICS 332312). OSHA activity number 344128459.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- MOFFITT WEST
- Site address
- 3100 JUANITA DR.
- City
- DENISON
- State
- TX
- ZIP
- 75020
- Mailing
- 3100 JUANITA DR., DENISON, TX 75020
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 332312
- Employees
- 16
- Ownership type
- A
Citations
3 citations on file for this inspection.
1910.305 B03 II
- Issued
- Jul 9, 2019
- Penalty
- Initial $361 · Current $217 Reduced
General-duty citation text
29 CFR 1910.305(b)(3)(ii): 29 CFR 1910.305(b)(3)(ii): Boxes shall be closed by suitable covers securely fastened in place, boxes were not closed as required. On the north west wall of the production area, the employer did not ensure the electrical panel box used to energize machinery and lights were effectively closed during operations, exposing employees to electrical shock hazards and inadvertent energization of equipment..
Recent events (2)
- — I (O) $216.6
- — Z (O) $361
1910.303 E
- Issued
- Jul 9, 2019
- Penalty
- Initial $361 · Current $217 Reduced
General-duty citation text
29 CFR 1910.303(e): Markings were not provided on electrical equipment giving voltage, current, wattage, and other ratings as necessary. In the production shop, the employer had electrical panel boxes that energized machinery that were not marked with voltage rating, exposing employees to electrical shock hazards.
Recent events (2)
- — I (O) $216.6
- — Z (O) $361
1910.304 F01 VIII
- Issued
- Jul 9, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.304(f)(1)(viii): 29 CFR 1910.304(f)(1)(viii): Circuit breakers used as switches in 120-volt and 277-volt, fluorescent lighting circuits were not listed and marked "SWD." In the production shop at the north wall, the employer allowed employees to turn fluorescent lights on and off from the electrical panel boxes and circuits that were not listed and marked "SWD" exposing employees to electrical shock hazards.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections in this industry (NAICS 332312)
More inspections in TX
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 344128459.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.