CHARLOTTE AMALIE, VI —
OSHA Inspection: MAFOLIE HOTEL & RESTAURANT
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of MAFOLIE HOTEL & RESTAURANT in MAFOLIE HOTEL & RESTAURANT 7091 ESTATE MAFOLIE, CHARLOTTE AMALIE, VI 00802 (NAICS 721110). OSHA activity number 344132329.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- MAFOLIE HOTEL & RESTAURANT
- Site address
- MAFOLIE HOTEL & RESTAURANT 7091 ESTATE MAFOLIE
- City
- CHARLOTTE AMALIE
- State
- VI
- ZIP
- 00802
- Mailing
- MAFOLIE HOTEL & RESTAURANT 7091 ESTATE MAFOLIE, CHARLOTTE AMALIE, VI 00802
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 721110
- Employees
- 31
- Ownership type
- A
Citations
3 citations on file for this inspection.
1910.303 G01
- Issued
- Oct 31, 2019
- Abate by
- Nov 27, 2019
- Penalty
- Initial $3,978 · Current $2,785 Reduced
General-duty citation text
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment. a. On or about 06/26/2019, at the restaurant kitchen area of the Mafolie Hotel and Restaurant, the electrical service panel in the area was not readily accessible. The electrical service panel was blocked with a steel table, a microwave oven, several boxes, and bags, bottles and cans of cooking ingredients and supplies. Note: Certification and documentation of abatement must be submitted for this citation item as required by 29 CFR 1903.19(c) and (d), respectively.
Recent events (3)
- — F (S) $2784.6
- — C (S) $3978
- — Z (S) $3978
1910.305 J02 IV
- Issued
- Oct 31, 2019
- Abate by
- Nov 27, 2019
- Penalty
- Initial $744 · Current $521 Reduced
General-duty citation text
29 CFR 1910.305(j)(2)(iv): A receptacle installed in a wet or damp location was not suitable for the location: a. On or about 06/26/2019, at the exterior side of the kitchen sink wall, an unsuitable, indoor type, electric branch circuit receptacle was installed outdoors in a damp location and exposed to the rain. Note: Certification and documentation of abatement must be submitted for this citation item as required by 29 CFR 1903.19(c) and (d), respectively.
Recent events (3)
- — F (O) $520.8
- — C (O) $744
- — Z (O) $744
1910.38 B
- Issued
- Oct 31, 2019
- Abate by
- Nov 27, 2019
- Penalty
- Initial $744 · Current $521 Reduced
General-duty citation text
29 CFR 1910.38(b): An emergency action plan was not in writing, kept in the workplace, and available to employees for review. a. On or about 06/26/2019, at the Mafolie Hotel and Restaurant, Saint Thomas, USVI, the employer failed to have a written emergency action plan establishing guidance and procedures to be executed by all employees in the event of an emergency. NOTE: Certification and documentation of abatement must be submitted for this citation item as required by CFR 1903.19(c).
Recent events (3)
- — F (O) $520.8
- — C (O) $744
- — Z (O) $744
More inspections at Mafolie Hotel & Restaurant
View Mafolie Hotel & Restaurant's full OSHA safety record →
More inspections in this industry (NAICS 721110)
More inspections in VI
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 344132329.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.