OSHA Inspection: SDR DISTRIBUTION SERVICES USA INC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of SDR DISTRIBUTION SERVICES USA INC. in 1245 FLOREST PARKWAY, PAULSBORO, NJ 08066 (NAICS 493110). OSHA activity number 344132949.

Watch SDR Distribution Services USA INC. — free Get an email when a new federal OSHA severe-injury report for SDR Distribution Services USA INC. is published. One employer, no account, unsubscribe in one click.
Site address
1245 FLOREST PARKWAY
City
PAULSBORO
State
NJ
ZIP
08066
Mailing
1245 FLOREST PARKWAY, PAULSBORO, NJ 08066
Inspection type
Complaint (B)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
493110
Employees
54
Ownership type
A

4 citations on file for this inspection.

1910.141 A03

Serious Gravity 1 1 instance 10 exposed
Issued
Abate by
Penalty
Initial $3978.00 · Current $2500.00 Reduced
29 CFR 1910.141(a)(3): The employer did not ensure that all places of employment were kept clean to the extent that the nature of the work allowed.    a)  SDR Distribution Services USA Inc.- Receiving area: Employees are exposed to tripping hazards from multiple telecommunication cables dangling from the ceiling level.  Observed on or about 07/02/2019.
Recent events (2)
  • — I (S) $2500
  • — Z (S) $3978

1910.178 G02

Serious Gravity 1 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $3978.00 · Current $2500.00 Reduced
29 CFR 1910.178(g)(2):  Battery charging apparatus for industrial trucks located in battery changing and charging installation was not protected from damage by trucks:    a) SDR Distribution Services USA Inc.- Forklift charging area:  The facility did not protect the battery charging apparatuses from damage.  The charging cables on the Enforcer battery charger model #EF3-12-550, S/N HD50214 had damaged cords with exposed copper conduit and the charger outer casing was damaged, observed on or about 07/02/2019.
Recent events (2)
  • — I (S) $2500
  • — Z (S) $3978

1910.303 B07 IV

Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $6630.00 · Current $3750.00 Reduced
29 CFR 1910.303(b)(7)(iv): Electric equipment had damaged parts that may adversely affect safe operation or mechanical strength of the equipment, such as parts that are broken, bent, cut, or deteriorated by corrosion, chemical action, or overheating:    a) SDR Distribution Services USA Inc. - Receiving area next to the conference room:  Employees are exposed to shock hazards by contacting exposed/damaged wires.  The electrical panel has a missing cover and is located next to a damp area. Observed on or about 07/02/2019.
Recent events (2)
  • — I (S) $3750
  • — Z (S) $6630

1910.305 E01

Serious Gravity 5 1 instance 10 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(e)(1): Cabinets, cutout boxes, fittings, boxes, and panelboard enclosures in wet locations were not weatherproof:  a) SDR Distribution Services USA Inc. - Receiving area next to the conference room:  Employees are exposed to shock hazards by contacting exposed/damaged wires.  The electrical panel has a missing cover and is located next to a damp area. The panel box is not water proof.  Observed on or about 07/02/2019.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

SPEEDX