Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: BRUCE & MERRILEES ELECTRIC COMPANY

Federal Agency inspection · Safety discipline

On , OSHA opened a federal Agency safety inspection of BRUCE & MERRILEES ELECTRIC COMPANY in 23RD & DUSS AVENUE, AMBRIDGE, PA 15003 (NAICS 238210). OSHA activity number 344159983.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Bruce & Merrilees Electric Company — free Get an email when a new federal OSHA severe-injury report for Bruce & Merrilees Electric Company is published. One employer, no account, unsubscribe in one click.
Site address
23RD & DUSS AVENUE
City
AMBRIDGE
State
PA
ZIP
15003
Mailing
930 CASS STREET, NEW CASTLE, PA 16101
Inspection type
Federal Agency (M)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
2
Ownership type
A

3 citations on file for this inspection.

1910.332 B02

Other-than-serious Gravity 10 1 instance 1 exposed
Issued
Dec 30, 2019
Abate by
Jan 27, 2020
Penalty
Initial $13,260 · Current $11,000 Reduced
1910.332(b)(2) Additional requirements for unqualified persons. Employees who are covered by paragraph (a) of this section but who are not qualified persons shall also be trained in and familiar with any electrically related safety practices not specifically addressed by 1910.331 through 1910.335 but which are necessary for their safety. 29 CFR 1910.332(a): The training requirements contained in this section apply to employees who face a risk of electric shock that is not reduced to a safe level by the electrical installation requirements of 1910.303 through 1910.308:   a) Jobsite, 23rd Street & Duss Avenue, Ambridge, PA:  On July 17, 2019, an employee was working to assist in applying labels to conductors within the ICO cabinet.  The employee was not sufficiently trained to recognize their exposure to live electrical hazards.
Recent events (3)
  • — J (O) $11000
  • — C (S) $13260
  • — Z (S) $13260

1910.333 C02

Other-than-serious Gravity 10 2 instances 3 exposed
Issued
Dec 30, 2019
Abate by
Jan 27, 2020
Penalty
Initial $13,260 · Current $11,000 Reduced
1910.333(c)(2) "Work on energized equipment." Only qualified persons may work on electric circuit parts or equipment that have not been deenergized under the procedures of paragraph (b) of this section. Such persons shall be capable of working safely on energized circuits and shall be familiar with the proper use of special precautionary techniques, personal protective equipment, insulating and shielding materials, and insulated tools. 29 CFR 1910.333(a)(1): The employer failed to ensure that live parts were deenergized before employees began to work on or near live parts:  a) Jobsite, 23rd & Duss Avenue, Ambridge, PA: On or about July 17, 2019, employees were identifying and labeling conductors inside a 480v three-phase energized control cabinet. An employee was electrocuted when contact was made with a conductor(s) from the middle phase of the output (load) side of the variable frequency motor control drive.    b) Jobsite, 23rd & Duss Avenue, Ambridge, PA: On or about July 1, 2019, employees were identifying and labeling conductors inside a 480v three-phase energized control cabinet.
Recent events (3)
  • — J (O) $11000
  • — C (S) $13260
  • — Z (S) $13260

1910.335 A01 II

Other-than-serious Gravity 10 1 instance 2 exposed
Issued
Dec 30, 2019
Abate by
Jan 27, 2020
Penalty
Initial $0 · Current $0
1910.335(a)(1)(ii) Protective equipment shall be maintained in a safe, reliable condition and shall be periodically inspected or tested, as required by 1910.137. 29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not provided with electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected and for the work being performed:  a) Facility, 23rd Street & Duss Avenue, Ambridge, PA: On or about July 17, 2019, employees were exposed to electrical shock, arcing parts, and electrocution hazards in that testing was performed on live parts of electrical equipment within the ICO cabinet without voltage rated gloves and face shields.
Recent events (3)
  • — J (O) $0
  • — C (S) $0
  • — Z (S) $0

View Bruce & Merrilees Electric Company's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 344159983.