WESTMINSTER, MA —
OSHA Inspection: MAYHEW BASQUE PLASTICS, LLC
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of MAYHEW BASQUE PLASTICS, LLC in 100 SIMPLEX DR, WESTMINSTER, MA 01473 (NAICS 326199). OSHA activity number 344174909.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- MAYHEW BASQUE PLASTICS, LLC
- Site address
- 100 SIMPLEX DR
- City
- WESTMINSTER
- State
- MA
- ZIP
- 01473
- Mailing
- 100 SIMPLEX DR, WESTMINSTER, MA 01473
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 326199
- Employees
- 60
- Ownership type
- A
Citations
9 citations on file for this inspection.
1910.145 C02 I
- Issued
- Dec 9, 2019
- Penalty
- Initial $9,282 · Current $4,641 Reduced
General-duty citation text
29 CFR 1910.145(c)(2)(i): Caution signs were not used to warn against potential hazards or to caution against unsafe practices: (a) Site: On the production floor, at the Pneumatic Handle Press, in the facility at 100 Simplex Drive, Westminster, MA 01453: On 7/9/2019 Caution signs were not used to warn against the struck by/pinch point hazard at the point of operations and did not warn against placing hands or other body parts in the point of operation.
Recent events (2)
- — I (S) $4641
- — Z (S) $9282
1910.212 A01
- Issued
- Dec 9, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.212(a)(1): One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks: (a) Site: On the production floor, at the Pneumatic Handle Press, in the facility at 100 Simplex Drive, Westminster, MA 01453: On 7/9/2019 one or more methods of machine guarding, such as but not limited to a fixed guard, light curtain, or appropriately configured two hand control, was not provided to protect the operator and other employees in the machine area from hazards created by the press point of operation.
Recent events (2)
- — I (O) $0
- — Z (S) $0
1910.147 C04 II
- Issued
- Dec 9, 2019
- Abate by
- Jan 28, 2020
- Penalty
- Initial $9,282 · Current $0 Reduced
General-duty citation text
29 CFR 1910.147(c)(4)(ii): Procedures did not clearly and specifically outline the scope, purpose, authorization, rules, and techniques to be utilized for the control of hazardous energy, and the means to enforce compliance including, but not limited to, 29 CFR 1910.147(c)(4)(ii)(A), (c)(4)(ii)(B), (c)(4)(ii)(C) and (c)(4)(ii)(D): (a) Site: On the production floor, at Van Dorn 350 Ton Press #1019, in the facility at 100 Simplex Drive, Westminster, MA 01453: On 7/23/2019 the Energy Control Procedure did not clearly and specifically outline the scope, purpose, authorization, rules, and techniques to be used for the control of hazardous energy, and the means to enforce compliance - including the steps for removal of lockout devices or tagout devices - with the result that an employee improperly applied LOTO procedures while performing work on the machine.
Recent events (2)
- — I (O) $0
- — Z (S) $9282
1910.147 C06 I C
- Issued
- Dec 9, 2019
- Abate by
- Jan 28, 2020
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.147(c)(6)(i)(C): Where lockout was used for energy control, the periodic inspection did not include a review, between the inspector and each authorized employee, of that employee's responsibilities under the energy control procedure being inspected. (a) Site: On the production floor, at Van Dorn 350 Ton Press #1019, in the facility at 100 Simplex Drive, Westminster, MA 01453: On 7/23/2019 where lockout was used for energy control a LOTO inspector did not review the inspection results from the Van Dorn 350 Ton Press #1019 with each authorized employee before that employee performed maintenance on the machine.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.333 B02 I
- Issued
- Dec 9, 2019
- Abate by
- Jan 28, 2020
- Penalty
- Initial $9,282 · Current $4,641 Reduced
General-duty citation text
29 CFR 1910.333(b)(2)(i): The employer did not maintain a written copy of the procedures outlined in paragraph (b)(2) of 29 CFR 1910.333 and did not make it available for inspection by the Assistant Secretary of Labor and his or her authorized representatives: (a) Site: On the production floor, at Van Dorn 350 Ton Press #1019, in the facility at 100 Simplex Drive, Westminster, MA 01453: On 7/23/2019 the employer had not developed a written procedure to address the electrical safety hazards when an employee would be exposed to contact with parts of fixed electric equipment or circuits which had been deenergized.
Recent events (2)
- — I (S) $4641
- — Z (S) $9282
1910.333 B02 II B
- Issued
- Dec 9, 2019
- Abate by
- Jan 28, 2020
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.333(b)(2)(ii)(B): Control circuit devices, such as push buttons, selector switches, and interlocks, were used as the sole means for deenergizing circuits and equipment: (a) Site: On the production floor, at Van Dorn 350 Ton Press #1019, in the facility at 100 Simplex Drive, Westminster, MA 01453: On 7/23/2019 an emergency stop was used as the sole means for deenergizing circuits and equipment.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.333 C02
- Issued
- Dec 9, 2019
- Abate by
- Jan 28, 2020
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.333(c)(2): The employer did not ensure that only qualified persons worked on electric circuit parts or equipment that had not been deenergized under the procedures of paragraph (b) of this section. (a) Site: On the production floor, at Van Dorn 350 Ton Press #1019, in the facility at 100 Simplex Drive, Westminster, MA 01453: On 7/23/2019 an employee who did not possess the knowledge required of a qualified person worked on a 480 volt electric circuit and he did not possess skills and knowledge regarding arc flash hazards involved with the equipment.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.333 C08
- Issued
- Dec 9, 2019
- Abate by
- Jan 28, 2020
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.333(c)(8): Conductive articles of jewelry and clothing (such a watch bands, bracelets, rings, key chains, necklaces, metalized aprons, cloth with conductive thread, or metal headgear) were worn where they might have contacted exposed energized parts, and were not rendered nonconductive by covering, wrapping, or other insulating means. (a) Site: On the production floor, at Van Dorn 350 Ton Press #1019, in the facility at 100 Simplex Drive, Westminster, MA 01453: On 7/23/2019 an employee was testing live circuits and was in direct contact with the electrical components in an open panel and wore a conductive belt buckle which might have contacted exposed energized parts, and was not rendered nonconductive by covering, wrapping, or other insulating means.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.335 A01 I
- Issued
- Dec 9, 2019
- Abate by
- Jan 28, 2020
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not using electrical protective equipment that was appropriate for the specific parts of the body to be protected and for the work to be performed: (a) Site: On the production floor, at Van Dorn 350 Ton Press #1019, in the facility at 100 Simplex Drive, Westminster, MA 01453: On 7/23/2019 employees were testing live circuits and were in direct contact with the open panel and employees were not using electrical protective equipment that was appropriate for the specific parts of the body to be protected and for the work to be performed.
Recent events (2)
- — I (S) $0
- — Z (S) $0
More inspections at Mayhew Basque Plastics, LLC
View Mayhew Basque Plastics, LLC's full OSHA safety record →
More inspections in this industry (NAICS 326199)
More inspections in MA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 344174909.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.