OSHA Inspection: S.B. BALLARD CONSTRUCTION COMPANY

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of S.B. BALLARD CONSTRUCTION COMPANY in GOETHALS AND BLACK ROAD, FORT BELVOIR, VA 22060 (NAICS 236220). OSHA activity number 344176987.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch S.B. Ballard Construction Company — free Get an email when a new federal OSHA severe-injury report for S.B. Ballard Construction Company is published. One employer, no account, unsubscribe in one click.
Site address
GOETHALS AND BLACK ROAD
City
FORT BELVOIR
State
VA
ZIP
22060
Mailing
2828 SHIPPS CORNER ROAD, VIRGINIA BEACH, VA 23456
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
236220
Employees
98
Ownership type
A

2 citations on file for this inspection.

1926.404 B01 II

Other-than-serious 1 instance 15 exposed
Issued
Oct 10, 2019
Abate by
Nov 6, 2019
Penalty
Initial $3,381 · Current $1,691 Reduced
29 CFR 1926.404(b)(1)(ii): On a construction site, where an assured equipment grounding program was not utilized, all 120-volt, single-phase, 15 and 20 ampere receptacle outlets which were not a part of the permanent wiring of the building or structure and which are in use by employees did not have approved ground fault circuit interrupters for personal protection:  a)    Fort Belvoir: On or about 07/24/109, a Trailer Blazer 325 diesel welder, 12,000 Watt generator that did not have ground-fault circuit-interrupter protection was used to energize 120-volt portable electrical equipment.  Abatement certification required within 10 days after abatement date.  The certification shall include a statement that abatement is complete, date and method of abatement, and states employees and their representatives were informed of this abatement.
Recent events (2)
  • — I (O) $1690.5
  • — Z (S) $3381

1926.403 B02

Other-than-serious 1 instance 15 exposed
Issued
Oct 10, 2019
Abate by
Nov 6, 2019
Penalty
Initial $0 · Current $0
29 CFR 1926.403(b)(2): Listed, labeled, or certified equipment was not installed and used in accordance with instructions included in the listing, labeling, or certification:  a)     Fort Belvoir: On or about 07/24/2019, extension cords were not used in according to its listing and labeling in that extension cords were plugged one into another.   Abatement certification required within 10 days after abatement date.  The certification shall include a statement that abatement is complete, date and method of abatement, and states employees and their representatives were informed of this abatement.