Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: U.S. FOREST SERVICE, DARRINGTON RANGER STATION

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of U.S. FOREST SERVICE, DARRINGTON RANGER STATION in 1405 EMENS AVE N, DARRINGTON, WA 98241 (NAICS 115310). OSHA activity number 344179346.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch U.S. Forest Service, Darrington Ranger Station — free Get an email when a new federal OSHA severe-injury report for U.S. Forest Service, Darrington Ranger Station is published. One employer, no account, unsubscribe in one click.
Site address
1405 EMENS AVE N
City
DARRINGTON
State
WA
ZIP
98241
Mailing
1405 EMENS AVE N, DARRINGTON, WA 98241
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
115310
Employees
12
Ownership type
D

2 citations on file for this inspection.

1910.37 B06

Other-than-serious 2 instances 12 exposed
Issued
Sep 9, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(6): Each exit sign was not illuminated to a surface value of at least five foot-candles (54 lux) by a reliable light source and be distinctive in color. Self-luminous or electroluminescent signs that have a minimum luminance surface value of at least .06 footlamberts (0.21 cd/m2) are permitted:   a) Facility, where defective exit signage included:  1. Computer Room, where the hard wired exit sign located above the discharge door was not equipped with a working light bulb.  2. Carpenter Shop Workout Room, where a paper exit sign was located above the discharge door.
Recent events (1)
  • — Z (O) $0

1910.303 G01 II

Other-than-serious 1 instance 12 exposed
Issued
Sep 9, 2019
Abate by
Oct 25, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(1)(ii): Working space for equipment likely to require examination, adjustment, servicing, or maintenance while energized was used for storage:   a) Printer Room, where the Xerox printer and the HP printer were placed on a desk and stored in front of circuit panel labeled D Computer Room.