Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: SCRANTON MOTORS, INC.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of SCRANTON MOTORS, INC. in 777 TALCOTTVILLE ROAD, VERNON, CT 06066 (NAICS 441110). OSHA activity number 344182142.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Scranton Motors, INC. — free Get an email when a new federal OSHA severe-injury report for Scranton Motors, INC. is published. One employer, no account, unsubscribe in one click.
Site address
777 TALCOTTVILLE ROAD
City
VERNON
State
CT
ZIP
06066
Mailing
777 TALCOTTVILLE ROAD, VERNON, CT 06066
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
441110
Employees
75
Ownership type
A

5 citations on file for this inspection.

1910.37 A04

Serious Gravity 1 1 instance 2 exposed
Issued
Aug 16, 2019
Abate by
Oct 3, 2019
Penalty
Initial $3,381 · Current $3,381
29 CFR 1910.37(a)(4): Safeguard(s) designed to protect employees during an emergency (e.g., sprinkler systems, alarm systems, fire doors, exit lighting), were not in proper working order at all times:  A.  On or about July 25, 2019, Reconditioning Shop:  The self-retracting arm on the identified emergency exit door was damaged and detatched from the door frame.  The defective safeguard would not keep the door closed in case of emergency.
Recent events (1)
  • — Z (S) $3381

1910.37 B06

Serious Gravity 1 1 instance 2 exposed
Issued
Aug 16, 2019
Abate by
Oct 3, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(6): Each exit sign was not illuminated to a surface value of at least five foot-candles (54 lux) by a reliable light source and be distinctive in color:  A.  On or about July 25, 2019, Reconditioning Shop:  The paper EXIT sign over the emergency exit was not self-illuminated, and there was no emergency lighting in the building.
Recent events (1)
  • — Z (S) $0

1910.303 B02

Serious Gravity 1 1 instance 3 exposed
Issued
Aug 16, 2019
Penalty
Initial $2,874 · Current $2,874
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:  A.  On or about July 25, 2019, Reconditioning Shop, Near the Office:  An Emerson Model MW11625B microwave oven was powered through a Carol 15A 3-way splitter, and not plugged directly into a wall outlet as per manufacturer's instructions.
Recent events (1)
  • — Z (S) $2874

1910.304 B04 II B

Serious Gravity 1 1 instance 3 exposed
Issued
Aug 16, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.304(b)(4)(ii)(B): Where connected to a branch circuit supplying two or more receptacles or outlets, a receptacle may not supply a total cord- and plug-connected load in excess of the maximum specified in Table S-4:  A.  On or about July 25, 2019, Reconditioning Shop, Near the Office:  A Carol 15A 3-way splitter was used in the bottom outlet of a 2-receptacle outlet box.  The splitter powered a timeclock, box fan and an Emerson Model MW11625B microwave oven at the same time.  The microwave had a draw of 12.5A, which increased fire risk.  Note:  Table S-4 allows a maximum load of 12 amperes on a receptacle rated at 15 amperes.
Recent events (1)
  • — Z (S) $0

1910.304 G05

Serious Gravity 1 1 instance 3 exposed
Issued
Aug 16, 2019
Abate by
Oct 3, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective:  A.  On or about July 25, 2019, Reconditioning Shop:  Voltage was detected in the metal parts of a white Westinghouse refrigerator, exposing employees to electric shock hazards.
Recent events (1)
  • — Z (S) $0

View Scranton Motors, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 344182142.