PEORIA, IL —
OSHA Inspection: AMEREN ILLINOIS
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of AMEREN ILLINOIS in 8420 N. UNIVERSITY STREET, PEORIA, IL 61615 (NAICS 221122). OSHA activity number 344194220.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- AMEREN ILLINOIS
- Site address
- 8420 N. UNIVERSITY STREET
- City
- PEORIA
- State
- IL
- ZIP
- 61615
- Mailing
- 8420 N. UNIVERSITY STREET, PEORIA, IL 61615
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 221122
- Employees
- 200
- Ownership type
- A
Citations
2 citations on file for this inspection.
1910.269 M03 II
- Issued
- Dec 9, 2019
- Abate by
- Jan 2, 2020
- Penalty
- Initial $11,934 · Current $11,934
General-duty citation text
1910.269(m)(3)(ii): Deenergizing lines and equipment for employee protection. The employer shall ensure that all switches, disconnectors, jumpers, taps, and other means through which known sources of electric energy may be supplied to the particular lines and equipment to be deenergized are open. The employer shall render such means inoperable, unless its design does not so permit, and then ensure that such means are tagged to indicate that employees are at work. On or about July 14, 2019, the employer did not ensure all means through which known sources of electric energy to be deenergized were open, and did not render such means inoperable with respect to its mobile substation which had been modified by the addition of a maintenance breaker.
Recent events (3)
- — F (S) $11934
- — C (S) $11934
- — Z (S) $11934
1910.269 D06
- Issued
- Dec 9, 2019
- Abate by
- Jan 2, 2020
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.269(d)(6): The established procedures for the application of energy control (the lockout or tagout procedures) did not include the following elements and actions, and these procedures were not performed in the following sequence: On or about July 29, 2019, employees were exposed to electrical hazards while performing maintenance activities on a mobile substation that had been modified by the addition of a maintenance breaker. The employer failed to implement energy control application steps as all energy isolating devices needed to control the energy to the mobile substation were not operated in such a manner to isolate the equipment from the energy source. As a result, the remaining energy control elements involving lockout or tagout devices [(d)(6)(iv)], dissipation of residual or stored energy [(d)(6)(v)], verification of isolation [(d)(6)(vi), were not implemented to protect the employees from electrical hazards during the maintenance activities.
Recent events (3)
- — F (S) $0
- — C (S) $0
- — Z (S) $0
More inspections at Ameren Illinois
View Ameren Illinois's full OSHA safety record →
More inspections in this industry (NAICS 221122)
More inspections in IL
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 344194220.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.