COLORADO SPRINGS, CO —
OSHA Inspection: WESTERN ACCEPTANCE LLC.
Complaint inspection · Health discipline
At a glance
On , OSHA opened a complaint health inspection of WESTERN ACCEPTANCE LLC. in 6275 LAKE SHORE CT., COLORADO SPRINGS, CO 80915 (NAICS 325411). OSHA activity number 344201611.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- WESTERN ACCEPTANCE LLC.
- Site address
- 6275 LAKE SHORE CT.
- City
- COLORADO SPRINGS
- State
- CO
- ZIP
- 80915
- Mailing
- 6275 LAKE SHORE CT., COLORADO SPRINGS, CO 80915
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 325411
- Employees
- 24
- Ownership type
- A
Citations
3 citations on file for this inspection.
1910.106 H07 I A
- Issued
- Dec 6, 2019
- Abate by
- Mar 10, 2020
- Penalty
- Initial $2,273 · Current $1,363 Reduced
General-duty citation text
29 CFR 1910.106(h)(7)(i)(a): Precautions shall be taken to prevent the ignition of flammable vapors. Sources of ignition include but are not limited to open flames; lightning; smoking; cutting and welding; hot surfaces; frictional heat; static, electrical, and mechanical sparks; spontaneous ignition, including heat-producing chemical reactions; and radiant heat: (a) On or about July 30, 2019, and at times prior, employees of Western Acceptance LLC were exposed to flash fire hazards in that ethanol vapors were not prevented from escaping containers during processing in the lab used by ADM Labs LLC. Processing included but was not limited to, open-top transfers of denatured alcohol solutions and removal of ethanol from rotary evaporators by way of open gravity transfer. Measures were not taken to ensure sparks were prevented in the areas where processing occurred such as by using non-static producing buckets, bonding the containers during transfers, and ensuring only explosion proof equipment was used in the area. The electrical installations including outlets, switches, panel boxes, and conduit were not explosion proof, nor was the box fan used in the area. Abatement Note: Abatement certification is required for this item (see enclosed "Certification of Corrective Action Worksheet").
Recent events (2)
- — I (S) $1363
- — Z (S) $2273
1910.178 C02 IV
- Issued
- Dec 6, 2019
- Abate by
- Jan 10, 2020
- Penalty
- Initial $3,031 · Current $1,818 Reduced
General-duty citation text
29 CFR 1910.178(c)(2)(iv): Power-operated industrial trucks designated as DY, EE, or EX were not used in locations where volatile flammable liquids or flammable gases were handled, processed or used, but in which the hazardous liquids, vapors or gases were normally confined within closed containers or closed systems from which they could have escaped only in case of accidental rupture or breakdown of such containers or systems, or in the case of abnormal operation of equipment: (a) On or about August 18, 2019, and at times prior, employees were exposed to flash fire hazards from the Toyota Electric Forklift Truck, Model SFBDLI25 which is rated E. The forklift was used by ADM Labs LLC, and employees of Western Acceptance, to transport containers of ethanol, and was operated in areas where ethanol vapors were known to be released. Abatement Note: Abatement certification is required for this item (see enclosed "Certification of Corrective Action Worksheet").
Recent events (2)
- — I (S) $1818
- — Z (S) $3031
1910.307 C02 I
- Issued
- Dec 6, 2019
- Abate by
- Mar 10, 2020
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.307(c)(2)(i): Equipment, wiring methods, and installations of equipment in hazardous (classified) locations were not intrinsically safe, approved for the hazardous (classified) location, or safe for the hazardous (classified) location: (a) On or about July 30, 2019, and at times prior, employees were exposed to flash fire hazards in that the equipment and electrical installations including outlets, switches, panels, and conduit, in hazardous (classified) locations, were not approved for the hazardous (classified) location. Employees used denatured alcohol (ethanol) in the Cannabidiol (CBD) extraction process in the lab. An ethanol solution was regularly transferred from open-top buckets to an open-top DrainDroyds allowing vapors in the air during transfer and processing; ethanol was removed from rotary evaporates through a gravity transfer. These condition exposed employees to a flash fire hazard due to the potential for an ignition source in an area where flammable vapors were, or could have been, present. Abatement Note: Abatement certification is required for this item (see enclosed "Certification of Corrective Action Worksheet").
Recent events (2)
- — I (S) $0
- — Z (S) $0
More inspections at Western Acceptance LLC.
View Western Acceptance LLC.'s full OSHA safety record →
More inspections in this industry (NAICS 325411)
More inspections in CO
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 344201611.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.