Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: PIKE ELECTRIC, LLC

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of PIKE ELECTRIC, LLC in 226 SCHROCK ROAD, GARRETT, PA 15542 (NAICS 237130). OSHA activity number 344214333.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Pike Electric, LLC — free Get an email when a new federal OSHA severe-injury report for Pike Electric, LLC is published. One employer, no account, unsubscribe in one click.
Establishment
PIKE ELECTRIC, LLC
Site address
226 SCHROCK ROAD
City
GARRETT
State
PA
ZIP
15542
Mailing
100 PIKE WAY PO BOX 868, MOUNT AIRY, NC 27030
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
237130
Employees
4
Ownership type
A

5 citations on file for this inspection.

1926.950 B01 I

Serious Gravity 10 1 instance 4 exposed
Issued
Nov 21, 2019
Abate by
Jan 17, 2020
Penalty
Initial $13,260 · Current $12,000 Reduced
29 CFR 1926.950(b)(1)(i): Each employee shall be trained in, and familiar with, the safety-related work practices, safety procedures, and other safety requirements in this subpart that pertain to his or her job assignments.    (a) Jobsite 226 Schrock Road, Garrett, PA: On or about August 3, 2019, employees were not wearing a face shield when working on and exposed to live electrical parts in the battery storage containers.
Recent events (2)
  • — I (S) $12000
  • — Z (S) $13260

1926.950 B02 II

Deleted Serious Gravity 10 1 instance 4 exposed
Issued
Nov 21, 2019
Abate by
Dec 11, 2019
Penalty
Initial $0 · Current $0
29 CFR 1926.950(b)(2)(ii): Employees were not trained on the skills and techniques necessary to determine the nominal voltage of exposed live parts:  (a) Jobsite 226 Schrock Road, Garrett, PA: On or about August 3, 2019, employees working in the battery containers were not familiar with nominal voltage of the exposed live parts.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1926.960 C01 III A

Deleted Serious Gravity 10 1 instance 1 exposed
Issued
Nov 21, 2019
Abate by
Dec 11, 2019
Penalty
Initial $13,260 · Current $0 Reduced
29 CFR 1926.960(c)(1)(iii)(A): Employees were not insulated from energized parts through the use of rubber insulating gloves or rubber insulating gloves and sleeves worn in accordance with paragraph (c)(2) of this section:  (a) Jobsite- 226 Schrock Road, Garrett, PA: On or about August 3, 2019, employees working on live energized equipment were not insulated through the use of rubber insulating gloves while removing batteries.
Recent events (2)
  • — I (S) $0
  • — Z (S) $13260

1926.960 C01 III B

Deleted Serious Gravity 10 1 instance 4 exposed
Issued
Nov 21, 2019
Abate by
Dec 11, 2019
Penalty
Initial $0 · Current $0
29 CFR 1926.960(c)(1)(iii)(B): The energized part was not insulated from the employee and from any other conductive object at a different potential:  (a) Jobsite- 226 Schrock Drive, Garrett, PA: On or about August 3, 2019, employees using a cordless DeWalt drill were exposed to energized parts.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1926.960 G05 IV

Other-than-serious 1 instance 4 exposed
Issued
Nov 21, 2019
Abate by
Jan 17, 2020
Penalty
Initial $11,366 · Current $10,000 Reduced
29 CFR 1926.960(g)(5)(iv): The protection for the employee's head did not consist of head protection meeting � 1926.100(b)(2) and a faceshield with a minimum arc rating of 8 cal/cm2 if the estimated incident energy exposure is less than 13 cal/cm2 for exposures involving single-phase arcs in open air or 9 cal/cm2 for other exposures:    (a) Jobsite 226 Schrock Road, Garrett, PA: On or about August 3, 2019, employees were not wearing a faceshield while working in the battery storage containers and were exposed to as well as working on live electrical parts.
Recent events (2)
  • — I (O) $10000
  • — Z (S) $11366

View Pike Electric, LLC's full OSHA safety record →