SAN ANTONIO, TX ·
OSHA Inspection: ENTECH SALES AND SERVICE LLC
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of ENTECH SALES AND SERVICE LLC in 8202 SAND PEBBLE, SAN ANTONIO, TX 78250 (NAICS 811310). OSHA activity number 344223219.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- ENTECH SALES AND SERVICE LLC
- Site address
- 8202 SAND PEBBLE
- City
- SAN ANTONIO
- State
- TX
- ZIP
- 78250
- Mailing
- 8202 SAND PEBBLE, SAN ANTONIO, TX 78250
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- Yes
- Union status
- Non-union (B)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 811310
- Employees
- 400
- Ownership type
- Private (A)
Citations
5 citations on file for this inspection.
1910.332 B01
- Issued
- Dec 26, 2019
- Abate by
- Jan 10, 2020
- Penalty
- Initial $11,366 · Current $7,000 Reduced
General-duty citation text
29 CFR 1910.332(b)(1): Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments: Fire Riser Room, FACP, FDC; 10010 San Pedro office Building: On or about August 08, 2019 and at times prior thereto, employees performing load bank testing on an energized alternating terminal switch were exposed to electrical hazards and were not provided training by the employer to ensure understanding of the type and magnitude of energy being worked with and the methods and means needed for energy isolation and control.
Recent events (2)
- · I (S) $7000
- · Z (S) $11366
1910.333 B02
- Issued
- Dec 26, 2019
- Abate by
- Jan 10, 2020
- Penalty
- Initial $11,366 · Current $7,000 Reduced
General-duty citation text
29 CFR 1910.333(b)(2): While an employee was exposed to contact with parts of fixed electric equipment or circuits which were deenergized, the circuits energizing the parts were not locked out or tagged or both in accordance with the requirements of this paragraph (b) of 29 CFR 1910.333(b)(2): Fire Riser Room, FACP, FDC; 10010 San Pedro office building: On or about August 08, 2019, and at times prior thereto, employees performing load bank testing on an alternating terminal switch were exposed to electrical hazards, and had not ensured the generator powering the alternating terminal switch had been effectively locked out and tagged prior to performing the load bank test.
Recent events (2)
- · I (S) $7000
- · Z (S) $11366
1910.335 A01 I
- Issued
- Dec 26, 2019
- Abate by
- Jan 10, 2020
- Penalty
- Initial $11,366 · Current $5,000 Reduced
General-duty citation text
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not using electrical protective equipment that was appropriate for the specific parts of the body to be protected and for the work to be performed: Fire Riser Room, FACP, FDC; 10010 San Pedro Office Building: On or about August 08, 2019 and at times prior thereto, employees were exposed to electrical hazards while performing load bank testing procedures on an alternating terminal switch without adequate personal protective equipment such as but not limited to insulated gloves, arc flash jackets and coveralls, and arc flash gaiters.
Recent events (2)
- · I (S) $5000
- · Z (S) $11366
1910.335 A01 V
- Issued
- Dec 26, 2019
- Abate by
- Jan 10, 2020
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.335(a)(1)(v): Employees exposed to the danger of injury to the eyes or face from electric arcs or flashes or from flying objects resulting from electrical explosion did not wear protective equipment for the eyes or face: Fire Riser Room, FACP, FDC; 10010 San Pedro Office Building: On or about August 08, 2019 and at times prior thereto, employees were exposed to electrical hazards while performing load bank testing procedures on an alternating terminal switch without wearing adequate personal protective equipment such as but not limited to arc flash hoods, arc flash helmets and arc flash visors.
Recent events (2)
- · I (S) $0
- · Z (S) $0
1910.335 A02 I
- Issued
- Dec 26, 2019
- Abate by
- Jan 15, 2020
- Penalty
- Initial $11,366 · Current $5,000 Reduced
General-duty citation text
29 CFR 1910.335(a)(2)(i): When working near exposed energized conductors or circuit parts, each employee did not use insulated tools or handling equipment when the tools or handling equipment might have made contact with such conductors or parts: Fire Riser Room, FACP, FDC; 10010 San Pedro Office Building: On or about August 08, 2019 and at times prior thereto, employees were exposed to electrical hazards while performing load bank testing procedures on an alternating terminal switch while using non-insulated hand tools such as but not limited to Husky screwdrivers and wrenches, wire cutters, and craftsman wrenches.
Recent events (2)
- · I (S) $5000
- · Z (S) $11366
More inspections at Entech Sales and Service LLC
View Entech Sales and Service LLC's full OSHA safety record →
More inspections in this industry (NAICS 811310)
More inspections in TX
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 344223219.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.