FLUSHING, NY —
OSHA Inspection: ISS FACILITIES SERVICES INC.
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of ISS FACILITIES SERVICES INC. in LAGUARDIA AIRPORT TERMINAL C, FLUSHING, NY 11371 (NAICS 561720). OSHA activity number 344239181.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- ISS FACILITIES SERVICES INC.
- Site address
- LAGUARDIA AIRPORT TERMINAL C
- City
- FLUSHING
- State
- NY
- ZIP
- 11371
- Mailing
- 3963 LULLWATER MAIN NE, KENNESAW, GA 30144
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 561720
- Employees
- 200
- Ownership type
- A
Citations
5 citations on file for this inspection.
1910.333 A01
- Issued
- Feb 10, 2020
- Abate by
- Mar 6, 2020
- Penalty
- Initial $13,494 · Current $10,795 Reduced
General-duty citation text
29 CFR 1910.333(a)(1): Live parts to which an employee may be exposed were not deenergized before the employee works on or near them: (a) Old Boiler Room Pit - Pump panel was not deenergized before work began to relocate a strobe and an alarm up to the main floor; on or about 08/14/19. NOTE: IN ADDITION TO ABATEMENT CERTIFICATION, THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT DOCUMENTATION FOR THIS ITEM, FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $ 1,000.00 AS PER 29 CFR 1903.19.
Recent events (3)
- — C (S) $13494
- — F (S) $10795.2
- — Z (S) $13494
1910.334 C02
- Issued
- Feb 10, 2020
- Abate by
- Mar 6, 2020
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.334(c)(2): When there was a defect or evidence of damage that could expose an employee to injury, the defective or damaged item was not removed from service: (a) Old Boiler Room Pit - A Fluke Voltage Tester failed to recognize energized parts in the pump panel; on or about 08/14/19. NOTE: IN ADDITION TO ABATEMENT CERTIFICATION, THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT DOCUMENTATION FOR THIS ITEM, FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $ 1,000.00 AS PER 29 CFR 1903.19.
Recent events (3)
- — C (S) $0
- — F (S) $0
- — Z (S) $0
1910.147 C04 I
- Issued
- Feb 10, 2020
- Abate by
- Mar 6, 2020
- Penalty
- Initial $13,494 · Current $10,795 Reduced
General-duty citation text
29 CFR 1910.147(c)(4)(i): Procedures were not developed, documented and utilized for the control of potentially hazardous energy when employees were engaged in activities covered by this section: (a) Old Boiler Room Pit - Pump panel was not locked out before work began to relocate a strobe and an alarm up to the main floor. No procedure was developed; on or about 08/14/19. NOTE: IN ADDITION TO ABATEMENT CERTIFICATION, THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT DOCUMENTATION FOR THIS ITEM, FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $ 1,000.00 AS PER 29 CFR 1903.19.
Recent events (3)
- — C (S) $13494
- — F (S) $10795.2
- — Z (S) $13494
1910.147 C05 I
- Issued
- Feb 10, 2020
- Abate by
- Mar 6, 2020
- Penalty
- Initial $13,494 · Current $10,795 Reduced
General-duty citation text
29 CFR 1910.147(c)(5)(i): Locks, tags, chains, wedges, key blocks, adapter pins, self-locking fasteners, or other hardware were not provided by the employer for isolating, securing or blocking of machines or equipment from energy sources: (a) Old Boiler Room Pit - Locks or tags were not provided to isolate the breaker that controlled the pump panel; on or about 08/14/19. NOTE: IN ADDITION TO ABATEMENT CERTIFICATION, THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT DOCUMENTATION FOR THIS ITEM, FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $ 1,000.00 AS PER 29 CFR 1903.19.
Recent events (3)
- — C (S) $13494
- — F (S) $10795.2
- — Z (S) $13494
1910.147 C07 I
- Issued
- Feb 10, 2020
- Abate by
- Mar 6, 2020
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.147(c)(7)(i): The employer did not provide adequate training to ensure that the purpose and function of the energy control program was understood by employees: (a) Old Boiler Room Pit - For the pump panel; on or about 08/14/19. NOTE: IN ADDITION TO ABATEMENT CERTIFICATION, THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT DOCUMENTATION FOR THIS ITEM, FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $ 1,000.00 AS PER 29 CFR 1903.19.
Recent events (3)
- — C (S) $0
- — F (S) $0
- — Z (S) $0
More inspections at ISS Facilities Services INC.
View ISS Facilities Services INC.'s full OSHA safety record →
More inspections in this industry (NAICS 561720)
More inspections in NY
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 344239181.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.