Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: EJ ELECTRIC T&D, LLC

Federal Agency inspection · Safety discipline

On , OSHA opened a federal Agency safety inspection of EJ ELECTRIC T&D, LLC in 1390 NY ROUTE 17A, WARWICK, NY 10990 (NAICS 221121). OSHA activity number 344246921.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch EJ Electric T&D, LLC — free Get an email when a new federal OSHA severe-injury report for EJ Electric T&D, LLC is published. One employer, no account, unsubscribe in one click.
Site address
1390 NY ROUTE 17A
City
WARWICK
State
NY
ZIP
10990
Mailing
53 NORTH PLAINS INDUSTRIAL ROAD, WALLINGFORD, CT 06492
Inspection type
Federal Agency (M)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
221121
Employees
80
Ownership type
A

2 citations on file for this inspection.

1910.269 L03 III

Deleted Serious Gravity 10 1 instance 2 exposed
Issued
Feb 6, 2020
Abate by
Feb 13, 2020
Penalty
Initial $9,446 · Current $0 Reduced
29 CFR 1910.269(l)(3)(iii): The employer did not ensure that no employee approached or took any conductive object closer to exposed energized parts than the employer's established minimum approach distance, unless provisions described in (l) (3) (iii) (A) - (C) were followed:    a) 1390 NY Route 17A, Warwick, NY, on August 19, 2019, and at times prior, two lineman were tightening slacked guy wires near energized conductors within the minimum approach distance of 3 feet and 4 inches ; the guy wires contacted energized conductors electrocuting the lineman.
Recent events (3)
  • — F (S) $0
  • — C (S) $9446
  • — Z (S) $9446

1910.269 Q02 I

Deleted Serious Gravity 10 1 instance 2 exposed
Issued
Feb 6, 2020
Abate by
Feb 12, 2020
Penalty
Initial $9,446 · Current $0 Reduced
29 CFR 1910.269(q)(2)(i): The employer failed to use the tension-stringing method, barriers, or other equivalent measures when installing or removing conductors and cables lines that can contact energized power lines or equipment.  a) 1390 NY Route 17A, Warwick, NY, on August 19, 2019, and at times prior, the employer was tightening two slacked guy wires that were close to energized conductors, when the guy wires contacted the energized conductor(s) electrocuting the lineman.
Recent events (3)
  • — F (S) $0
  • — C (S) $9446
  • — Z (S) $9446

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 344246921.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.