Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: AMERIMAX, INC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of AMERIMAX, INC. in 3025 BOWLERAMA DRIVE, NEW CASTLE, DE 19720 (NAICS 493110). OSHA activity number 344257670.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Amerimax, INC. — free Get an email when a new federal OSHA severe-injury report for Amerimax, INC. is published. One employer, no account, unsubscribe in one click.
Establishment
AMERIMAX, INC.
Site address
3025 BOWLERAMA DRIVE
City
NEW CASTLE
State
DE
ZIP
19720
Mailing
3025 BOWLERAMA DRIVE, NEW CASTLE, DE 19720
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
493110
Employees
13
Ownership type
A

3 citations on file for this inspection.

1910.303 B02

Serious Gravity 5 2 instances 3 exposed
Issued
Feb 3, 2020
Abate by
May 11, 2020
Penalty
Initial $3,084 · Current $1,542 Reduced
29 CFR 1910.303(b)(2): Installation and use. Listed or labeled equipment shall be installed and used in accordance with any instructions included in the listing or labeling.    a) Throughout the warehouse of 3025 Bowlerama Drive, New Castle, DE: On or about August 23, 2019, the employer failed to ensure relocatable power taps (RPT) used to power computer workstations, printers, fans, electric stingers, and digital scales, were directly connected to a permanent outlet.    a) Throughout the warehouse of 3025 Bowlerama Drive, New Castle, DE: On or about August 23, 2019, the employer failed to ensure relocatable power taps (RPT) used to power computer workstations, printers, fans, electric stingers, and digital scales, were not connected in series to extension cords.    Abatement Note:  Underwriters Laboratories (UL), refers to power strips as Relocatable Power Taps (RPTs) and, in its "General Information for Electrical Equipment Directory" (sometimes called the UL white book or UL Directory) contains instructions that require UL-listed RPTs to be directly connected to a permanently installed branch circuit receptacle; they are not to be series-connected to other RPTs or connected to extension cords.
Recent events (2)
  • — I (S) $1542
  • — Z (S) $3084

1910.305 G01 IV A

Serious Gravity 5 1 instance 3 exposed
Issued
Feb 3, 2020
Abate by
May 11, 2020
Penalty
Initial $3,084 · Current $1,542 Reduced
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:    a) Throughout the warehouse of 3025 Bowlerama Drive, New Castle, DE: On or about August 23, 2019, the employer failed to ensure flexible cords (extension cords and relocatable power taps) were not used in lieu of of fixed wiring.  Multiple extension cords connected in series to provide power to workstations, exposing employees to electrical and fire hazards.
Recent events (2)
  • — I (S) $1542
  • — Z (S) $3084

1910.305 G01 IV D

Serious Gravity 5 1 instance 3 exposed
Issued
Feb 3, 2020
Abate by
May 11, 2020
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(D): Flexible cords and cables not specifically permitted otherwise in paragraph (g)(1)(ii) of this section, were used where attached to building surfaces:     a) Throughout the warehouse of 3025 Bowlerama Drive, New Castle, DE: On or about August 23, 2019, the employer allowed flexible cords (extension cords) to be attached to building surfaces to include ceilings, walls, and poles, exposing the employees to electrical and fire hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 344257670.