Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: ROSS VALVE MFG. CO. INC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of ROSS VALVE MFG. CO. INC. in 79 102ND ST.SUITE 100, TROY, NY 12181 (NAICS 332919). OSHA activity number 344258009.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Ross Valve MFG. CO. INC. — free Get an email when a new federal OSHA severe-injury report for Ross Valve MFG. CO. INC. is published. One employer, no account, unsubscribe in one click.
Site address
79 102ND ST.SUITE 100
City
TROY
State
NY
ZIP
12181
Mailing
79 102ND ST.SUITE 100, TROY, NY 12181
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
332919
Employees
45
Ownership type
A

3 citations on file for this inspection.

1910.303 B02

Deleted Serious Gravity 1 1 instance 4 exposed
Issued
Dec 18, 2019
Abate by
Jan 7, 2020
Penalty
Initial $4,347 · Current $0 Reduced
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:  (a) Valve test pit area:   On or prior to 8/22/19, a wall-mounted transformer located below the disconnect for jib crane was not installed in accordance with it's listing and labelling in that it was a single phase, step down type transformer with a primary voltage rating of 600V and secondary voltage rating of 120/240V.  The transformer had been wired as a step-up type to output 575V three-phase.
Recent events (3)
  • — F (S) $0
  • — C (S) $4347
  • — Z (S) $4347

1910.305 E02

Other-than-serious Gravity 5 2 instances 4 exposed
Issued
Dec 18, 2019
Abate by
Jul 10, 2020
Penalty
Initial $7,246 · Current $3,500 Reduced
29 CFR 1910.305(e)(2): Switches, circuit breakers and switchboards installed in wet locations were not enclosed in weatherproof enclosures:  (a) Valve test pit area:   On or prior to 8/22/19, disconnect for jib crane along wall (to right of the clock) was not enclosed in a weather-proof enclosure and had been covered with plastic sheeting.  (b) Valve test pit area:  On or prior to 8/22/19, disconnect located at the base of the jib crane was not enclosed in weatherproof enclosure and the enclosure was damaged; the disconnect was covered with plastic sheeting to protect it from water.
Recent events (3)
  • — F (O) $3500
  • — C (S) $7246
  • — Z (S) $7246

1910.305 J02 IV

Deleted Serious Gravity 5 1 instance 4 exposed
Issued
Dec 18, 2019
Abate by
Jan 7, 2020
Penalty
Initial $0 · Current $0
29 CFR 1910.305(j)(2)(iv): A receptacle installed in a wet or damp location was not suitable for the location:  (a) Valve test pit area:   On or prior to 8/22/19, Leviton 2433 16-20R twist-lock connector(s) for valve actuators and related test equipment, were not rated for use in damp or wet locations, exposing employees to a shock hazard.
Recent events (3)
  • — F (S) $0
  • — C (S) $0
  • — Z (S) $0

View Ross Valve MFG. CO. INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 344258009.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.