OSHA Inspection: TADBIK NJ, INC

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of TADBIK NJ, INC in 17 MADISON RD, FAIRFIELD, NJ 07004 (NAICS 323111). OSHA activity number 344263744.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Tadbik NJ, INC — free Get an email when a new federal OSHA severe-injury report for Tadbik NJ, INC is published. One employer, no account, unsubscribe in one click.
Establishment
TADBIK NJ, INC
Site address
17 MADISON RD
City
FAIRFIELD
State
NJ
ZIP
07004
Mailing
17 MADISON RD, FAIRFIELD, NJ 07004
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
323111
Employees
43
Ownership type
A

5 citations on file for this inspection.

1910.36 D01

Serious Gravity 10 1 instance 5 exposed
Issued
Jan 27, 2020
Penalty
Initial $12,145 · Current $4,600 Reduced
29 CFR 1910.36(d)(1): Employees must be able to open an exit route door from the inside at all times without keys, tools, or special knowledge. A device such as a panic bar that locks only from the outside was not provided.    Location: 17 Madison Rd, Fairfield, NJ. .    a) In the event of an emergency some employees may require special knowledge on how to operate the door in its current condition. There was no panic bar provided at the emergency door in the shipping area; on or about 8/27/19.
Recent events (2)
  • — I (S) $4600
  • — Z (S) $12145

1910.37 B05

Serious Gravity 5 3 instances 40 exposed
Issued
Jan 27, 2020
Penalty
Initial $6,940 · Current $4,600 Reduced
29 CFR 1910.37(b)(5): Each doorway or passage along an exit access that could be mistaken for an exit was not marked "Not an Exit" or similar designation, or be identified by a sign indicating its actual use (e.g. closet).    Location: 17 Madison Rd., Fairfield, NJ.    a) Employer did not provide "Not an Exit" signs at the facility along the emergency passage way; on or about 8/27/19.
Recent events (2)
  • — I (S) $4600
  • — Z (S) $6940

1910.147 C07 I

Serious Gravity 10 1 instance 1 exposed
Issued
Jan 27, 2020
Penalty
Initial $12,145 · Current $4,600 Reduced
29 CFR 1910.147(c)(7)(i): The employer did not provide adequate training to ensure that the purpose and function of the energy control program was understood by employees.    Location: 17 Madison Rd., Fairfield, NJ.    a) An employee suffered injuries to his hand when he bypassed the guarding of the MA2 machine (Mark Andy printing press) he was operating in order to clear a problem with the slitter trim at the die cutting area of the machine.  The employee did not understand thus did not use Lock Out/Tag Out procedures; on or about 8/27/19.
Recent events (2)
  • — I (S) $4600
  • — Z (S) $12145

1910.303 G01 I B

Serious Gravity 1 1 instance 10 exposed
Issued
Jan 27, 2020
Penalty
Initial $5,205 · Current $4,600 Reduced
29 CFR 1910.303(g)(1)(i)(B): The width of working space in front of the electric equipment shall be the width of the equipment or 762 mm (30 in.), whichever is greater. In all cases, the working space shall permit at least a 90-degree opening of equipment doors or hinged electrical panels.     Location: 17 Madison Rd., Fairfield, NJ.    a) Employer did not ensure that the working width in front of the electrical panel located in the production area was greater than 30 inches; on or about 8/27/19.
Recent events (2)
  • — I (S) $4600
  • — Z (S) $5205

1910.303 G02 I

Serious Gravity 5 1 instance 5 exposed
Issued
Jan 27, 2020
Penalty
Initial $6,940 · Current $4,600 Reduced
29 CFR 1910.303(g)(2)(i): Live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by approved cabinets of other forms of approved enclosures, or other means listed under this provision.    Location: 17 Madison Rd, Fairfield, NJ.     a) An electrical panel at the production area did not have an enclosure.  Employees were exposed to electrical shock; on or about 8/27/19.
Recent events (2)
  • — I (S) $4600
  • — Z (S) $6940

View Tadbik NJ, INC's full OSHA safety record →