LAWRENCEVILLE, GA —
OSHA Inspection: SKIPPER LOGISTICS INC.
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of SKIPPER LOGISTICS INC. in 753 WINER INDUSTRIAL WAY STE A, LAWRENCEVILLE, GA 30046 (NAICS 493110). OSHA activity number 344272612.
Where did this inspection happen?
- Establishment
- SKIPPER LOGISTICS INC.
- Site address
- 753 WINER INDUSTRIAL WAY STE A
- City
- LAWRENCEVILLE
- State
- GA
- ZIP
- 30046
- Mailing
- 753 WINER INDUSTRIAL WAY STE A, LAWRENCEVILLE, GA 30046
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 493110
- Employees
- 20
- Ownership type
- A
Citations
6 citations on file for this inspection.
5(a)(1)
- Issued
- Abate by
- Penalty
- Initial $4774.00 · Current $4774.00
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which was free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to: industrial storage rack collapse and struck by hazards: On or about 8/29/2019 in the warehouse area workers on foot and or operating powered industrial equipment were exposed to struck by and crushing hazards where the loaded industrial storage racks were visibly damaged by powered industrial trucks at locations including but not limited to: a. D28 - stretcher bent b. E28 - stretcher bent c. G27 - stretcher bent d. G13 - damaged upright e. H34 - stretcher bent f. I34 - stretcher bent g. J16 - stretcher bent h. K15 - stretcher bent i. L33 - stretcher bent j. L33 - shelf bent (unloaded/available for use) k. L16 - stretcher bent l. M16 - stretcher bent m. N16 - stretcher bent n. N16 - stretcher bent o. Q7 - stretcher bent p. Q8 - shelf bent (loaded) q. Q13 - stretcher bent r. Q18 - stretcher bent s. Q17 - stretcher bent t. R25 - stretcher bent u. R8 - stretcher bent v. S15 - stretcher bent w. T16 - stretcher bent One feasible means of abatement would be to maintain the structural integrity of the installed rack system by assuring proper operational, housekeeping, and maintenance procedures including but not limited to: Regularly inspect for damage. If damage is found, IMMEDIATELY unload the affected area and replace or repair any damaged columns, beams, or other structural components."
Recent events (1)
- — Z (S) $4774
1910.157 E02
- Issued
- Abate by
- Penalty
- Initial $1534.00 · Current $1534.00
General-duty citation text
29 CFR 1910.157(e)(2): Portable fire extinguishers were not visually inspected at least monthly: a. On or about 8/29/2019, throughout the facility workers expected to fight incipient level fires were exposed to smoke inhalation and burn hazards where the employer failed to inspect the portable fire extinguishers since installed in 12/17/2018. b. On or about 8/29/2019, there was an extinguisher mounted to the Linde E25C powered industrial truck that was installed on 7/24/2018 that was not inspected monthly.
Recent events (1)
- — Z (S) $1534
1910.178 A04
- Issued
- Abate by
- Penalty
- Initial $1534.00 · Current $1534.00
General-duty citation text
29 CFR 1910.178(a)(4): Modifications and additions which affect capacity and safe operation of powered industrial truck were performed by the employer without the manufacturer's prior written approval: On or about 8/12/2019, in the Validation shipment area #2, powered industrial truck operators were observed exposed to injuries resulting from tip-over where the employer allowed for the use of fork extensions to be used which could change center of balance.
Recent events (1)
- — Z (S) $1534
1910.303 B02
- Issued
- Penalty
- Initial $1304.00 · Current $1304.00
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: a. On or about 8/29/2019, at the Validation Shipping area #2, employees were observed exposed to electrical hazards where the electrical service did not meet listed labeling where the 15 A relocatable power tap (RPT) powered a 1 A phone charger/speaker cord, an 11 A printer, an 8 A Bosch battery charger, a 2 A internet router, a .3 A computer monitor, and a red extension cord powering a 1.2 A scale. Additionally, portable heaters were also powered by the same RPT. b. On or about 8/29/2019, at the Picking shipment area #2, an employee was observed exposed to electrical hazards where the electrical service did not meet listed labeling where the 15 A relocatable power tap (RPT), powered by the green extension cord, powered an orange extension cord powering a .8 A Lasko box fan, a 500mA scale, a 500mA scale, and a 13 A Ryobi 7 3/4-inch circular saw S/N CSB125. Additionally, portable heaters were also powered by the same RPT. c. On or about 8/29/2019, at the shipping workstation, workers were exposed to electrical hazards where the metallic, quad outlet was attached to a flexible cord being used as a pendant. d. On or about 8/29/2019, at the shipping workstation, workers were exposed to electrical hazards where the metallic, quad outlet powered a relocatable power tap (RPT) that powered a red extension cord that powered another RPT powering the bubble wrap machine. The metallic, quad outlet also powered an RPT that powered an RPT powering a personal fan, a printer, a printer, and a monitor. The metallic, quad outlet also powered an internet router. Additionally, portable heaters were also powered by the same metallic, quad outlet. e. On or about 8/29/2019, at the shipping workshop, workers were exposed to electrical hazards where the 15 A relocatable power tap (RPT) was powered by an orange extension cord. The RPT powered a 2 A internet router, a 1.5 A label printer, an 11 A Xerox printer, and a .3 A monitor. Additionally, portable heaters were also powered by the same RPT.
Recent events (1)
- — Z (S) $1304
1910.305 G01 IV A
- Issued
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: a. On or about 8/29/2019, at the Picking shipment area #2, where an employee was observed exposed to electrical hazards where the electrical service did not meet listed labeling where the 15 A relocatable power tap (RPT), powered by the zip tied green extension cord being used as permanent wiring, powered an orange extension cord powering a .8 A Lasko box fan, a 500mA scale, a 500mA scale, and a 13 A Ryobi 7 3/4-inch circular saw S/N CSB125. Additionally, at times where the weather was colder portable heaters were also powered by the same RPT. b. On or about 8/29/2019, at the shipping workshop, workers were exposed to electrical hazards where the 15 A relocatable power tap (RPT) was powered by a zip tied orange extension cord being used as permanent wiring. The RPT powered a 2 A internet router, a 1.5 A label printer, an 11 A Xerox printer, and a .3 A monitor. Additionally, at times where the weather was colder portable heaters were also powered by the same RPT. c. On or about 8/29/2019, at the shipping workstation, workers were exposed to electrical hazards where the metallic, quad outlet was attached to a flexible cord being used as permanent wiring.
Recent events (1)
- — Z (S) $0
1910.303 B01 IV
- Issued
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.303(b)(1)(iv): Electric equipment was not free from recognized hazards that were likely to cause serious physical harm to employees, such as damaged electrical insulation: a. On or about 8/29/2019, at the battery charging area, METEK 880H3-18C charger, S/N 215CS33495, where employees were exposed to electrical hazards where there was exposed copper on the DC (RED) cable. b. On or about 8/29/2019, at the battery charging area, METEK 750H3-18C charger, S/N 215CS30948, where employees were exposed to electrical hazards where there was previously exposed copper on the DC (RED) cable, repaired with electricians tape.
Recent events (1)
- — Z (O) $0
More inspections at SKIPPER LOGISTICS INC.
LAWRENCEVILLE, GA—2019-08-29 00:00:00
SKIPPER LOGISTICS INC.
LAWRENCEVILLE, GA—2015-11-05 00:00:00
SKIPPER LOGISTICS INC.
View SKIPPER LOGISTICS INC.'s full OSHA safety record →
More inspections in this industry (NAICS 493110)
PORTSMOUTH, VA—2026-07-15
DACS INC
WEST CHESTER, OH—2026-07-14
CRESCENT PARK CORPORATION
WEYMOUTH, MA—2026-07-14
SPEEDX
DUNDALK, MD—2026-07-09
WILLIAMS SCOTSMAN, INC.
ROCK HILL, SC—2026-07-08
77566 - WEST MARINE INC
More inspections in GA
GREENSBORO, GA—2026-07-16
PURE BEAUTY FARMS, INC.
FOREST PARK, GA—2026-07-16
POLYNT COMPOSITES USA INC.
AUGUSTA, GA—2026-07-16
GF CASTING SOLUTIONS AUGUSTA, LLC
CHAMBLEE, GA—2026-07-16
U.S. DEPARTMENT OF TREASURY
DECATUR, GA—2026-07-15
PALLETS ACQUISITION LLC
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 344272612.