Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: D & S PLATING CO., INC.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of D & S PLATING CO., INC. in 102 CABOT STREET, HOLYOKE, MA 01040 (NAICS 332813). OSHA activity number 344288436.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch D & S Plating CO., INC. — free Get an email when a new federal OSHA severe-injury report for D & S Plating CO., INC. is published. One employer, no account, unsubscribe in one click.
Site address
102 CABOT STREET
City
HOLYOKE
State
MA
ZIP
01040
Mailing
102 CABOT STREET, HOLYOKE, MA 01040
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
332813
Employees
13
Ownership type
A

2 citations on file for this inspection.

1910.303 B06

Serious Gravity 5 3 instances 12 exposed
Issued
Dec 12, 2019
Abate by
Jan 16, 2020
Penalty
Initial $3,789 · Current $1,896 Reduced
29 CFR 1910.303(b)(6): Conductors or equipment were located in damp or wet locations; where exposed to gases, fumes, vapors, liquids, or other agents that had a deteriorating effect on the conductors or equipment; or where exposed to excessive temperatures and were not identified for use in the operating environment:    Nitric Acid dip tank room, 102 Cabot Street, Holyoke, MA: On or about September 5, 2019 employees were using equipment such as but not limited to light switches, pumps, and flexible cords connected to receptacles which were located in a damp location and were exposed to gasses and vapors from Nitric acid. Nitric Acid vapors have deteriorating effects on both conductors and electrical equipment had not been not identified for use in such an environment.
Recent events (2)
  • — I (S) $1895.5
  • — Z (S) $3789

1910.305 E02

Serious Gravity 5 15 instances 12 exposed
Issued
Dec 12, 2019
Abate by
Jan 16, 2020
Penalty
Initial $3,789 · Current $0 Reduced
29 CFR 1910.305(e)(2): Switches, circuit breakers and switchboards installed in wet locations were not enclosed in weatherproof enclosures:    Throughout facility, 102 Cabot Street, Holyoke, MA: On or about September 5, 2019 employees were using electrical equipment such as but not limited to submersible pumps and fans which were connected to receptacles above fluid tanks and the receptacles were not enclosed in waterproof enclosures.
Recent events (2)
  • — I (S) $0
  • — Z (S) $3789

View D & S Plating CO., INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 344288436.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.