Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: INDICOM ELECTRIC COMPANY, LLC

Unprogrammed Related inspection · Safety discipline

On , OSHA opened an unprogrammed Related safety inspection of INDICOM ELECTRIC COMPANY, LLC in 600 N. COMMERCE, AURORA, IL 60504 (NAICS 238210). OSHA activity number 344299441.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Indicom Electric Company, LLC — free Get an email when a new federal OSHA severe-injury report for Indicom Electric Company, LLC is published. One employer, no account, unsubscribe in one click.
Site address
600 N. COMMERCE
City
AURORA
State
IL
ZIP
60504
Mailing
1026 MOEN AVE., ROCKDALE, IL 60436
Inspection type
Unprogrammed Related (G)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
1
Ownership type
A

3 citations on file for this inspection.

1910.332 B01

Serious Gravity 10 1 instance 1 exposed
Issued
Nov 25, 2019
Abate by
Mar 2, 2020
Penalty
Initial $9,282 · Current $6,000 Reduced
29 CFR 1910.332(b)(1): Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments:    On or about September 10, 2019 a electrician performed servicing tasks, such as opening 600 volt switch gear, that contained energized electrical components.  The employee was trained in, but not familiar with safety-related work practices including the purpose and necessity of wearing electrical personal protective equipment, such as but not limited to, leather protectors, ear canal inserts and a face shield when working on or near energized components at or above 50 volts.  Employees were exposed to the hazards of shock, electrocution and arc flash/blast injuries.        Abatement documentation is required of this item in accordance with the requirements of 29 CFR 1903.19(d).
Recent events (2)
  • — I (S) $6000
  • — Z (S) $9282

1910.333 A

Serious Gravity 10 1 instance 1 exposed
Issued
Nov 25, 2019
Abate by
Mar 2, 2020
Penalty
Initial $0 · Current $0
29 CFR 1910.333(a): Safety-related work practices were not employed to prevent electric shock or other injuries resulting from either direct or indirect electrical contacts, when work was performed near or on equipment or circuits which were or could be energized:    On or about September 10, 2019, an employee performed preventative maintenance such as unbolting switch gear covers for thermal imaging, near energized electrical components.  The employee did not utilize safety-related work practices to prevent injuries from direct or indirect electrical contacts, such as by wearing properly selected electrical personal protective equipment or shielding at all times when working on or near energized components up to 600 volts.         Abatement documentation is required of this item in accordance with the requirements of 29 CFR 1903.19(d).
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.335 A01 I

Serious Gravity 10 1 instance 1 exposed
Issued
Nov 25, 2019
Abate by
Dec 10, 2019
Penalty
Initial $9,282 · Current $6,000 Reduced
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not using electrical protective equipment that was appropriate for the specific parts of the body to be protected and for the work to be performed:   On or about September 10, 2019, an employee removing bolted covers on an energized General Electric Spectra Series 600 volt switch gear did not wear the electrical protective equipment appropriate for the level of exposure, to protect against electrocution and arc flash/blast injuries, including:    1)  Hand protection: Leather gloves.   2)  Apparel: Arc-rated clothing such as arc-rated long-sleeve shirt and pants or arc-rated coverall.        3)  Head and face protection: Arc-rated face shield, arc-rated hard hat, arc-rated flash suit hood and/or balaclava.         4)  Hearing protection: Hearing protectors (canal inserts).           Abatement documentation is required of this item in accordance with the requirements of 29 CFR 1903.19(d).
Recent events (2)
  • — I (S) $6000
  • — Z (S) $9282

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 344299441.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.