On , OSHA opened a referral safety inspection of U.C. HEALTH, LLC in 151 WEST GALBRAITH ROAD, CINCINNATI, OH 45216 (NAICS 622110). OSHA activity number 344338686.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch U.C. Health, LLC — free Get an email when a new federal OSHA severe-injury report for U.C. Health, LLC is published. One employer, no account, unsubscribe in one click.
Establishment
U.C. HEALTH, LLC
Site address
151 WEST GALBRAITH ROAD
City
CINCINNATI
State
OH
ZIP
45216
Mailing
151 WEST GALBRAITH ROAD, CINCINNATI, OH 45216
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
622110
Employees
650
Ownership type
A

2 citations on file for this inspection.

1910.147 D

Serious Gravity 10 2 instances 4 exposed
Issued
Nov 26, 2019
Abate by
Dec 23, 2019
Penalty
Initial $13,260 · Current $7,956 Reduced
29 CFR 1910.147(d): Application of control. The established procedures for the application of energy control (the lockout or tagout procedures) shall cover the following elements and actions and shall be done in the following sequence:         (1)Preparation for shutdown. Before an authorized or affected employee turns off a machine or equipment, the authorized employee shall have knowledge of the type and magnitude of the energy, the hazards of the energy to be controlled, and the method or means to control the energy.    (2)Machine or equipment shutdown. The machine or equipment shall be turned off or shut down using the procedures established for the machine or equipment. An orderly shutdown must be utilized to avoid any additional or increased hazard(s) to employees as a result of the equipment stoppage.   (3)Machine or equipment isolation. All energy isolating devices that are needed to control the energy to the machine or equipment shall be physically located and operated in such a manner as to isolate the machine or equipment from the energy source(s).    a) On or about September 22, 2019 employees who perform maintenance on the exhaust fan in West Pavilion 2nd floor roof were not required to:    (1) Turn off and shut down the main disconnect for the fan.  (2) Physically locate and operate energy isolating devices in such a manner as to isolate machine or equipment  from the other energy source  (3) Affix a lockout or tagout devices to energy isolating device(s)
Recent events (2)
  • — I (S) $7956
  • — Z (S) $13260

1910.147 C05 I

Serious Gravity 10 1 instance 4 exposed
Issued
Nov 26, 2019
Abate by
Dec 23, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.147(c)(5)(i): Locks, tags, chains, wedges, key blocks, adapter pins, self-locking fasteners, or other hardware shall be provided by the employer for isolating, securing or blocking of machines or equipment from energy sources.  a) On or about September 22, 2019 while performing maintenance on the exhaust fan, lockout device(s) were not attached to the electrical disconnect and a screw driver was used to prevent the movement of the belt for the exhaust fan.