Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: CRETE CORE INGREDIENTS

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of CRETE CORE INGREDIENTS in 2220 COUNTY ROAD 1, CRETE, NE 68333 (NAICS 311119). OSHA activity number 344348834.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Crete Core Ingredients — free Get an email when a new federal OSHA severe-injury report for Crete Core Ingredients is published. One employer, no account, unsubscribe in one click.
Site address
2220 COUNTY ROAD 1
City
CRETE
State
NE
ZIP
68333
Mailing
2220 COUNTY ROAD 1, CRETE, NE 68333
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
311119
Employees
126
Ownership type
A

4 citations on file for this inspection.

1910.37 B05

Serious Gravity 1 1 instance 1 exposed
Issued
Feb 19, 2020
Abate by
Apr 6, 2020
Penalty
Initial $3,384 · Current $2,369 Reduced
29 CFR 1910.37(b)(5): Each doorway or passage along an exit access that could be mistaken for an exit must be marked "Not an Exit" or similar designation, or be identified by a sign indicating its actual use (e.g., closet):     The employer is failing to ensure that employees are protected from fire hazards. This was most recently documented at 2220 County Road I, Crete, Nebraska 68333 on October 1, 2019.  The employer did not ensure that a door that was not to be used as an exit was marked by a sign reading Not an Exit. Doors used for travel between two interior rooms in the PF MCC Room was not marked with a sign reading Not an Exit.
Recent events (2)
  • — I (S) $2368.8
  • — Z (S) $3384

1910.119 E03 VII

Serious Gravity 5 1 instance 1 exposed
Issued
Feb 19, 2020
Abate by
Apr 6, 2020
Penalty
Initial $5,309 · Current $3,716 Reduced
29 CFR 1910.119(e)(3)(vii): The employer did not ensure that the process hazard analysis (PHA) had a complete qualitative evaluation of a range of the possible safety and health effects of failures of controls:     The employer is failing to ensure that the process hazard analysis (PHA) had a complete qualitative evaluation of a range of the possible safety and health effects of failures of controls. This violation was most recently documented at a worksite located at or near 2220 County Road I, Crete, Nebraska 68333 on October 1, 2019. The process hazard analysis (PHA) was completed in January 2017. However, the PHA did not fully address qualitative evaluation of a range of the possible safety and health effects of failures of controls including, but not limited to; having an incomplete evaluation on the PHA  Unit: Refrigeration System +34 Cooler Air Unit. There was an evaluation of the loss of containment if the unit was hit by a forklift or manlift; however, the consequences in regard to the possible injury did not detail what the actual injuries could be.
Recent events (2)
  • — I (S) $3716.3
  • — Z (S) $5309

1910.119 N

Serious Gravity 5 1 instance 1 exposed
Issued
Feb 19, 2020
Abate by
Apr 6, 2020
Penalty
Initial $5,309 · Current $3,716 Reduced
29 CFR 1910.119(n): The emergency action plan did not include procedures for handling small releases:    The employer is failing to protect employees from chemical burn hazards associated with the anhydrous ammonia refrigeration system. This violation was most recently documented at a worksite located at or near 2220 County Road I, Crete, Nebraska 68333 on October 1, 2019. In the company written emergency action program there is no information for how employees are to differentiate between small releases and large releases and how to respond.
Recent events (2)
  • — I (S) $3716.3
  • — Z (S) $5309

1910.305 B01 II

Serious Gravity 5 1 instance 1 exposed
Issued
Feb 19, 2020
Penalty
Initial $4,513 · Current $3,159 Reduced
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed:    Employees are exposed to an electrical hazard.  This violation was most recently documented at a worksite located at or near 2220 County Road I, Crete, Nebraska 68333 on October 1, 2019. The employer did not ensure that an unused openings were closed for the electrical control boxes on Compressor 1 and Compressor 2 in the engine room.
Recent events (2)
  • — I (S) $3159.1
  • — Z (S) $4513

View Crete Core Ingredients's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 344348834.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.