CRETE, NE —
OSHA Inspection: CRETE CORE INGREDIENTS
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of CRETE CORE INGREDIENTS in 2220 COUNTY ROAD 1, CRETE, NE 68333 (NAICS 311119). OSHA activity number 344348834.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- CRETE CORE INGREDIENTS
- Site address
- 2220 COUNTY ROAD 1
- City
- CRETE
- State
- NE
- ZIP
- 68333
- Mailing
- 2220 COUNTY ROAD 1, CRETE, NE 68333
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 311119
- Employees
- 126
- Ownership type
- A
Citations
4 citations on file for this inspection.
1910.37 B05
- Issued
- Feb 19, 2020
- Abate by
- Apr 6, 2020
- Penalty
- Initial $3,384 · Current $2,369 Reduced
General-duty citation text
29 CFR 1910.37(b)(5): Each doorway or passage along an exit access that could be mistaken for an exit must be marked "Not an Exit" or similar designation, or be identified by a sign indicating its actual use (e.g., closet): The employer is failing to ensure that employees are protected from fire hazards. This was most recently documented at 2220 County Road I, Crete, Nebraska 68333 on October 1, 2019. The employer did not ensure that a door that was not to be used as an exit was marked by a sign reading Not an Exit. Doors used for travel between two interior rooms in the PF MCC Room was not marked with a sign reading Not an Exit.
Recent events (2)
- — I (S) $2368.8
- — Z (S) $3384
1910.119 E03 VII
- Issued
- Feb 19, 2020
- Abate by
- Apr 6, 2020
- Penalty
- Initial $5,309 · Current $3,716 Reduced
General-duty citation text
29 CFR 1910.119(e)(3)(vii): The employer did not ensure that the process hazard analysis (PHA) had a complete qualitative evaluation of a range of the possible safety and health effects of failures of controls: The employer is failing to ensure that the process hazard analysis (PHA) had a complete qualitative evaluation of a range of the possible safety and health effects of failures of controls. This violation was most recently documented at a worksite located at or near 2220 County Road I, Crete, Nebraska 68333 on October 1, 2019. The process hazard analysis (PHA) was completed in January 2017. However, the PHA did not fully address qualitative evaluation of a range of the possible safety and health effects of failures of controls including, but not limited to; having an incomplete evaluation on the PHA Unit: Refrigeration System +34 Cooler Air Unit. There was an evaluation of the loss of containment if the unit was hit by a forklift or manlift; however, the consequences in regard to the possible injury did not detail what the actual injuries could be.
Recent events (2)
- — I (S) $3716.3
- — Z (S) $5309
1910.119 N
- Issued
- Feb 19, 2020
- Abate by
- Apr 6, 2020
- Penalty
- Initial $5,309 · Current $3,716 Reduced
General-duty citation text
29 CFR 1910.119(n): The emergency action plan did not include procedures for handling small releases: The employer is failing to protect employees from chemical burn hazards associated with the anhydrous ammonia refrigeration system. This violation was most recently documented at a worksite located at or near 2220 County Road I, Crete, Nebraska 68333 on October 1, 2019. In the company written emergency action program there is no information for how employees are to differentiate between small releases and large releases and how to respond.
Recent events (2)
- — I (S) $3716.3
- — Z (S) $5309
1910.305 B01 II
- Issued
- Feb 19, 2020
- Penalty
- Initial $4,513 · Current $3,159 Reduced
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed: Employees are exposed to an electrical hazard. This violation was most recently documented at a worksite located at or near 2220 County Road I, Crete, Nebraska 68333 on October 1, 2019. The employer did not ensure that an unused openings were closed for the electrical control boxes on Compressor 1 and Compressor 2 in the engine room.
Recent events (2)
- — I (S) $3159.1
- — Z (S) $4513
More inspections at Crete Core Ingredients