Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: LANCASTER TANKS AND STEEL PRODUCTS INC.

Complaint inspection · Health discipline

On , OSHA opened a complaint health inspection of LANCASTER TANKS AND STEEL PRODUCTS INC. in 107 DOROTHY STREET, BUFFALO, NY 14206 (NAICS 331210). OSHA activity number 344355714.

Watch Lancaster Tanks AND Steel Products INC. — free Get an email when a new federal OSHA severe-injury report for Lancaster Tanks AND Steel Products INC. is published. One employer, no account, unsubscribe in one click.
Site address
107 DOROTHY STREET
City
BUFFALO
State
NY
ZIP
14206
Mailing
107 DOROTHY STREET, BUFFALO, NY 14206
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
331210
Employees
20
Ownership type
A

4 citations on file for this inspection.

1910.106 D04 IV

Serious Gravity 5 1 instance 5 exposed
Issued
Jan 14, 2020
Abate by
Feb 14, 2020
Penalty
Initial $2,577 · Current $1,288 Reduced
29 CFR 1910.106(d)(4)(iv): Mechanical exhaust system for the inside storage room was not controlled by a switch located outside of the door; and/or the ventilating equipment and lighting fixtures were not operated by the same switch: - a) Paint/solvent storage room - On or about 10/11/19, flammable materials are stored within the inside storage room.  The mechanical exhaust system and the lighting fixtures are not operated by the same switch.  ABATMENT CERTIFICATION REQUIRED
Recent events (3)
  • — J (S) $1288
  • — C (S) $2577
  • — Z (S) $2577

1910.107 C06

Deleted Serious Gravity 5 1 instance 5 exposed
Issued
Jan 14, 2020
Abate by
Feb 14, 2020
Penalty
Initial $2,576 · Current $0 Reduced
29 CFR 1910.107(c)(6): Electrical wiring and equipment outside of but within 20 feet of spraying area(s), and not separated by partitions, did not conform to the provisions for Class I, Division 2, hazardous locations:  a) Spray Booth Area - On or about 10/11/19, electrical outlets located within the spray area were not approved for Class 1 Division 2 hazardous locations.  ABATEMENT CERTIFICATION REQUIRED
Recent events (3)
  • — J (S) $0
  • — C (S) $2576
  • — Z (S) $2576

1910.107 E09

Serious Gravity 5 1 instance 2 exposed
Issued
Jan 14, 2020
Abate by
Jan 21, 2020
Penalty
Initial $2,576 · Current $1,288 Reduced
29 CFR 1910.107(e)(9): Flammable liquids for use in spraying operations were transferred from one container to another without both containers being effectively bonded and grounded to prevent discharge sparks of static electricity.  a) Spray Booth Area - On or about 10/11/19, PPG Amerlock 2/400 White Resin (FP=116 deg F), PPG Amerlock 2 Cure (FP=114 deg F), and xylene (FP=87 deg F) were transferred from their original containers to a 5 gallon mixing bucket without effectively bonding and grounding both containers to prevent discharge sparks of static electricity.  ABATEMENT CERTIFICATION REQUIRED
Recent events (3)
  • — J (S) $1288
  • — C (S) $2576
  • — Z (S) $2576

1910.107 G07

Other-than-serious 1 instance 5 exposed
Issued
Jan 14, 2020
Abate by
Jan 21, 2020
Penalty
Initial $0 · Current $0
29 CFR 1910.107(g)(7): "NO SMOKING" signs in large letters on contrasting color background were not conspicuously posted at all spraying areas and paint storage rooms.  a) Spray Booth Area - On or about 10/11/19, "NO SMOKING" signs were not posted in spray painting areas or in paint storage areas.  ABATEMENT CERTIFICATION REQUIRED
Recent events (3)
  • — J (O) $0
  • — C (O) $0
  • — Z (O) $0