TAMPA, FL —
OSHA Inspection: KINDER MORGAN PORT SUTTON TERMINAL LLC
Referral inspection · Health discipline
At a glance
On , OSHA opened a referral health inspection of KINDER MORGAN PORT SUTTON TERMINAL LLC in 4310 PENDOLA POINT ROAD, TAMPA, FL 33619 (NAICS 325311). OSHA activity number 344358569.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- KINDER MORGAN PORT SUTTON TERMINAL LLC
- Site address
- 4310 PENDOLA POINT ROAD
- City
- TAMPA
- State
- FL
- ZIP
- 33619
- Mailing
- 4310 PENDOLA POINT ROAD, TAMPA, FL 33619
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 325311
- Employees
- 30
- Ownership type
- A
Citations
4 citations on file for this inspection.
1910.36 G02
- Issued
- Jan 29, 2020
- Penalty
- Initial $6,554 · Current $3,932 Reduced
General-duty citation text
29 CFR 1910.36(g)(2): Exit access(es) were not at least 28 inches (71.1 cm) wide at all points. a) At warehouse #2, employees were exposed to an entrapment and fire hazard, in that, the door to exit the scale room #4 has an access width of 18 inches, as observed, on or about 10/02/2019.
Recent events (2)
- — I (S) $3932.4
- — Z (S) $6554
1910.109 I02 III B
- Issued
- Jan 29, 2020
- Abate by
- Mar 17, 2020
- Penalty
- Initial $8,193 · Current $0 Reduced
General-duty citation text
29 CFR 1910.109(i)(2)(iii)(b): Storage buildings did not have adequate ventilation or were not constructed to be self-ventilating in the event of fire. a) At warehouse #2 employer did not provide suitable ventilation or self-ventilation where ammonium nitrate was being stored and handled in case of a fire, as observed on or about 10/02/2019.
Recent events (2)
- — I (S) $0
- — Z (S) $8193
1910.109 I04 II B
- Issued
- Jan 29, 2020
- Abate by
- Mar 1, 2021
- Penalty
- Initial $0 · Current $4,916
General-duty citation text
29 CFR 1910.109(i)(4)(ii)(b): Wooden bins were not protected against impregnation by ammonium nitrate. a) At warehouse #2 employer did not ensure that the wooden bins used for storing ammonia nitrate were protected to prevent impregnation, as observed on or about 10/02/2019.
Recent events (3)
- — P (S) $4915.8
- — I (S) $4915.8
- — Z (S) $0
1910.157 C01
- Issued
- Jan 29, 2020
- Abate by
- Feb 25, 2020
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(c)(1): Portable fire extinguishers were not mounted, located and identified so that they were readily accessible without subjecting the employees to injuries: a) At warehouse #2 by bin #21 the fire extinguisher was blocked by ammonium nitrate preventing access to the fire extinguisher by the employees, as observed on or about 10/02/2019.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Kinder Morgan Port Sutton Terminal LLC
View Kinder Morgan Port Sutton Terminal LLC's full OSHA safety record →
More inspections in this industry (NAICS 325311)
More inspections in FL
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 344358569.