Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: US COAST GUARD BASE DETACHMENT BORINQUEN

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of US COAST GUARD BASE DETACHMENT BORINQUEN in USCG BASE DETACHMENT BORINQUEN 260 GUARD ROAD, AGUADILLA, PR 00603 (NAICS 928110). OSHA activity number 344407135.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch US Coast Guard Base Detachment Borinquen — free Get an email when a new federal OSHA severe-injury report for US Coast Guard Base Detachment Borinquen is published. One employer, no account, unsubscribe in one click.
Site address
USCG BASE DETACHMENT BORINQUEN 260 GUARD ROAD
City
AGUADILLA
State
PR
ZIP
00603
Mailing
USCG BASE DETACHMENT BORINQUEN 260 GUARD ROAD, AGUADILLA, PR 00603
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
928110
Employees
25
Ownership type
D

3 citations on file for this inspection.

1910.303 G01

Serious Gravity 1 2 instances 3 exposed
Issued
Feb 24, 2020
Abate by
Mar 19, 2020
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment.  a. On or about 10/18/2019, at the AC&R shop of the USCG Base Detachment Borinquen, the electrical service panel in the area was not readily accessible. The electrical service panel was blocked by a countertop/drawers cabinet, boxes, devices and materials stored in the floor below and in front, obstructing access.  b. On or about 10/18/2019, at the DC/Carpentry Shop of the USCG Base Detachment Borinquen, the electrical service panel in the area was not readily accessible. The panel was blocked by pieces of metal and a plastic five gallon bucket, placed in the floor below and in front, obstructing access.  NOTE:  Certification of abatement is not required for this citation item since it was submitted prior to citation issuance.
Recent events (1)
  • — Z (S) $0

1910.253 B04 III

Serious Gravity 5 1 instance 2 exposed
Issued
Feb 24, 2020
Abate by
Mar 19, 2020
Penalty
Initial $0 · Current $0
29 CFR 1910.253(b)(4)(iii):  An oxygen cylinder in storage was not separated from an acetylene fuel-gas cylinder, a minimum distance of 20 feet (6.1 m) or by a noncombustible barrier at least 5 feet (1.5 m) high having a fire-resistance rating of at least half an hour.  a. On or about 10/18/2019, at the Vehicle Maintenance Shop (VMS) of the USCG Base Detachment Borinquen, oxygen and acetylene compressed gas cylinders, were not separated by adequate distance or barrier while in storage. The cylinders were left together, uncapped and without the anticipation of gas been drawn, for a time period in excess of 24 hours.      NOTE:  Certification of abatement is not required for this citation item since it was submitted prior to citation issuance.
Recent events (1)
  • — Z (S) $0

1910.253 B01 II

Other-than-serious 1 instance 2 exposed
Issued
Feb 24, 2020
Abate by
Mar 19, 2020
Penalty
Initial $0 · Current $0
29 CFR 1910.253(b)(1)(ii): A compressed acetylene fuel-gas cylinder was not legibly marked, for the purpose of identifying its content, with either the chemical or the trade name of the gas.   a. On or about 10/18/2019, at the Vehicle Maintenance Shop (VMS) of the USCG Base Detachment Borinquen, a compressed acetylene fuel-gas cylinder was not legibly marked, by means of not readily removable stenciling, stamping, or labeling.   NOTE: Certification and documentation of abatement must be submitted for this citation item as required by 29 CFR 1903.19(c) and (d), respectively.